Enhanced Micro TDC 3000 User’s Manual 5-5 9/95
5.1.1
5.1.1.3 How to Load a US from Another Operating US
This procedure requires an operating HM that has been configured, initialized, and loaded
with the volumes, directories, and data defined in Table 4-1.
1. Call up the Console Status Display. To do this, from the Engineering Personality
Main Menu, select CONSOLE STATUS, or in the Operator Personality, press the
CONS STATUS key.
2. Select the node number for the US to be loaded. The node number turns white.
3. If the status for the US to be loaded is FAIL, READY, PWR_ON, or QUALIF, skip
to step 4. Otherwise, select SHUT DOWN, and press ENTER. This shuts down and
resets the other US.
4. If AUTOLOAD NET target is present, select AUTOLOAD NET and press ENTER,
(to load the Operator Personality) and skip to step 6. Otherwise, select MANUAL
LOAD. Four new targets appear. Continue with step 5.
5. Select either the OPERATOR PROGRAM or ENGINEER PROGRAM or
UNIVERSAL PROGRAM target, then follow the prompters that appear to select
the default source (NET = HM) for the program source and data source.
6. Wait for the Console Status display (Operator or Universal Personality) or the
Engineering Personality Main Menu (Engineering Personality) to appear. If the
Console Status display is on screen, go to subsection 5.1.1.5, Setting the Time and
Date.
If the menu does not appear within 5 minutes, something went wrong. Here are some
suggestions for recovery:
Try the procedure again.
Refer to the Process Operations Manual for information about status conditions that
affect the ability of a US to load.
Refer to Section 20 of the Engineer’s Reference Manual. This section has
information about causes of node loading failures, and memory dumps that may be
necessary to analyze such failures.
Use the System Startup Guide to start up the Enhanced Micro TDC 3000 System.
5.1.1.4 How to Change a US’s Personality
If you have the Universal Personality loaded, you can switch between operations functions
and engineering functions by holding down the Control key and pressing the Help key on
the Engineering Keyboard.
If you have two operating USs, use the steps under 5.1.1.3 to load one station from the
other. If you have only one US, use the procedure under 5.1.1.1 or 5.1.1.2 to reset it and
load it with the Operator Personality or the Universal Personality.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell Enhanced Micro TDC 3000 and is the answer not in the manual?

Honeywell Enhanced Micro TDC 3000 Specifications

General IconGeneral
BrandHoneywell
ModelEnhanced Micro TDC 3000
CategoryController
LanguageEnglish

Related product manuals