Flex 402 & Flex 404 Instruction Manual — P/N 52194:D4 3/27/2015 29
Installation of Optional Modules Installation
4XLMF LED Interface Module (Flex 404 only)
The 4XLMF supports the RZA-4XF Remote Annunciator module. The wiring of this module must
follow the requirements as specified in “Power-limited Wiring Requirements” on page 23.
Important: The 4XLMF module can only
be installed on connectors J3 and J5 of the Flex 404
main circuit board.
4XLB
Figure 2.15 4XLMF LED Interface Module
Front View of RZA-4XF
Side View
Single-gang Box
4XLMF Module
Note: Make wiring connections with system
power off. Maximum wire impedance is
50 ohms per wiring connection.
+24 VDC
Out #1
Out #2
Out #3
Out #4
System Trouble
Sound
Resound
1
2
3
4
5
6
7
8
Connect to corresponding terminals of
RZA-4XF Remote Annunciator
4xlma.wmf
rza-4xf.wmf