▪ Gateway: Gateway IP address
▪ Slave1 IP Addr: IP address of Slave1
▪ Slave2 IP Addr: IP address of Slave2
▪ Slave3 IP Addr: IP address of Slave3
▪ Slave1 UnitID: Unit ID of Slave1 used for the Modbus TCP port
▪ Slave2 UnitID: Unit ID of Slave2 used for the Modbus TCP port
▪ Slave3 UnitID: Unit ID of Slave3 used for the Modbus TCP port
• If you have selected Modbus RTU Interface, configure the following under
Modbus RTU Settings.
▪ Baud Rate: Select the baud rate used for the Modbus RTU serial port. Options
include: 9600,19200, 38400, 57600, 11520.
▪ Parity: The parity used for the Modbus RTU serial port. Options include: Even
and Odd.
▪ Stop Bits: Options include: 1 and 2.
▪ Byte Order: Select a byte order that matches the expected byte order of the
Modbus client. Options include: Big Endian, Little Endian, Big Endian Bytes
Swapped, and Little Endian Bytes Swapped.