EasyManuals Logo

Honeywell Galaxy Dimension GD-96 Installer Manual

Honeywell Galaxy Dimension GD-96
306 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #265 background imageLoading...
Page #265 background image
Galaxy Dimension Installer Manual
6-191
69 - Access Control (cont’d)
69.3.2 = Card Format
This option selects what type of card is used with the DCM reader. There are five options:
0 = 26 bit
1 = Crp 1K 35 bit
2 = 37 bit no FC
3 = Northern 34 bit
4 = Custom.
1 = Format Name
This option is only available when 4 = Custom is selected as the format. It gives a name to the custom format.
The maximum number of characters in the name is 12.
2 = Card Length
The bit size of the card can be 26, 27, 32, 34, 35, 37 or 40.
3 = Start Point
If the card structure is unknown then it can be decided where the card number starts from. This is a numeric
value that must be less than the maximum length of the card.
4 = User Field
This is where the facility code is specified. Two options can be selected:
1 = Field Position
This is the start bit for the facility code. It can be from 1 to the card number start point.
2 = Field Length
This is the length of the facility code. The maximum field length is from the field position to the start of the
card number.

Table of Contents

Other manuals for Honeywell Galaxy Dimension GD-96

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell Galaxy Dimension GD-96 and is the answer not in the manual?

Honeywell Galaxy Dimension GD-96 Specifications

General IconGeneral
BrandHoneywell
ModelGalaxy Dimension GD-96
CategoryControl Panel
LanguageEnglish

Related product manuals