Mounting and installation
12
Connecting the thermal actuators
 
Damage to the underoor 
heating controller.
Take the technical data into account at 
thermal actuators: 
Total of 3A maximum current, 250mA 
continuous current per zone.
!
Each zone can control up to 3 thermal actuators. 3 
thermal actuators can be connected directly for Zone 
1, 2 for Zone 2 and 1 thermal actuator each for Zones 
3 through 5. One connection for the expansion module 
is available for each of the zones 6 through 8.
If more than 11 thermal actuators are to be connected to 
the underfloor heating controller, the cables of the thermal 
actuators must be connected in a distribution box.
1
  If applicable, install the cables of the thermal 
actuators to the distribution box.
2
  Wire the wires of the thermal actuators.
3
  Break out the openings for the cables on 
the housing using a diagonal cutter.
14
  Strip the connections 5.5 mm (see 
fold-out page, Fig. 6).
5
  Insert the connecting cables of the thermal actuators 
into the cable openings of the connectors. 
6
  Close the terminals.    
7
  Plug the connectors into the sockets 
of the corresponding zones (see fold-
out page, Fig. 4 (Z1...Z8)).
8
  Clamp the cables into the stress relief clamp.
9
  Secure the cable with the cable clamp.
Connecting a pump 
(
230 V AC
)
As soon as a zone is active, the pump is 
activated with a time delay. The pump switches 
off as soon as all the valves are closed.
The LED   (see fold-out page, Fig. 3 (6)) lights 
up green when the pump is running.
The pump contact is not floating. The pump can 
be connected directly, see circuit diagram.
 
Damage to the underoor 
heating controller.
Short-circuit at incorrect installation.
Connect all the controllers 
to the same phase.
!
1
  Strip the connections 7 mm (see fold-out page, Fig. 7).
2
  Connect the pump (see fold-out page, Fig.4 (12)).
Installation Disassembling
1
2
Cabling – 
continued