Connection diagram for TC
The tightness test is carried out with the auxiliary
valves installed on TC 3 (pre-wired). The terminals
for the valve inputs remain vacant.
Mains voltage and control voltage:
24VDC/120VAC/230VAC
Mains voltage: 120VAC/230VAC,
control voltage: 24VDC
Finishing the wiring
9
Tightness test
All new connections between the valve and the
TC must be checked for tightness.
Pressurize the system. Do not exceed the maxi-
mum inlet pressure.
Soap off pipe connections.
Setting the test instant
The test instant (MODE) can be set using two
DIP switches.
Disconnect the unit from the electrical power
supply.
Before opening the unit, the fitter should ground
himself.
Unscrew the housing cover.
Set the test instant to Mode 1, 2 or 3.
Mode 1
t
M
5s
10s
15s
20s
25s
30s
Mode 1: test before burner start-up with incom-
ing thermostat/start-up signalϑ (factory setting).
Mode 1
Mode 2: test after burner run when the thermo-
stat/start-up signal ϑ drops and after switching
on the mains voltage.
The tightness test also starts after a reset.
Mode 2
Mode 3: test with incoming thermostat/start-up
signal ϑ before burner start-up and when the
thermostat/start-up signal ϑ drops after burner
run.
Mode 3
Invalid switch setting: no function. The
1
2
Power
LED
is permanently red, see page8 (Assistance
in the event of malfunction).
Continue on page 7 (Setting measurement
time tM).