Programming
62 MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
PAS/Pre-Signal Delay
Pressing 1 while viewing Edit Input Zone Screen #3 will display the following screen:
Pre-signal
The Pre-signal option programs the zone to delay panel activation for a preprogrammed time
delay of up to three minutes while allowing for visual verification by a person. Note that the
alarm relay and communicator will respond to the initial alarm immediately. To enable the Pre-
signal feature, press 2 while viewing PAS/Pre-Signal Screen. Refer to "Presignal" on page 115.
PAS
The PAS (Positive Alarm Sequence) option will program the zone to delay panel activation
(including alarm relay and communicator) for a period of 15 seconds plus a programmable time
of up to 3 minutes. To enable the PAS feature, press 3 while viewing the PAS/Pre-Signal
Screen. This option is available only for circuits programmed as smoke detector circuits. Refer
to "Positive Alarm Sequence" on page 115.
Freeze Supervision
Pressing 1 for Freeze Supv. while viewing Edit Input Zone Screen #4 programs the FACP to
supervise the devices connected to the selected zone for freeze conditions. Each press of the 1
key will toggle the display between Freeze Supv. Yes and No. The factory default setting is No
Freeze Supervision.
INPUT ZONE #
1=PAS/PRE-SIG DELAY
NO DELAY
Edit Input Zone Screen #3
PAS/PRE-SIG DELAY
1=NO DELAY
2=PRE-SIGNAL DELAY
3=PAS DELAY
PAS/Pre-Signal Delay Screen
See Page
See Page
INPUT ZONE #
1=FREEZE SUPV. NO
2=ACC MSG #
Edit Input Zone Screen #4