AM-8000 Manuale di installazione PAGE - 11
AM8000_manu-inst Doc. 160.1-AM8000-ITA Rev A.3 NOTIFIER ITALIA
NOTE:
Connect the 47K , ¼ W EOL
resistor only on last sounde
of the line
ATTENTION
:
Polarity displayed are in
Alarm condition, at idle
condition, they are inverted
Sounder connection - controlled output
Polarized devices (electronic sirens, etc.)
47 K
¼ W
3
4
Non-polarized devices (Bells, relays, etc.)
47 K
¼ W
2 x 1N 4004
3
4
Sounder output operation window
CNU
4 3
Siren output connections
(refer to basic board topography)
IDLE CUT SHORTCIRCUIT
21K 61K