PAGE - 12 Manuale di installazione AM-8000
NOTIFIER ITALIA Doc. 160.1-AM8000-ITA Rev A.3 AM8000_manu-inst
SYSTEM COMPONENTS
Black Box
Each Black Box is equipped of one CPU card and can contain up to 2 Loop Interface cards ( LIB-8000 )
Each LIB card can drive up to 2 ADV loop
Each ADV Loop line can connect up to 159 detector and 159 Modules in Advanced protocol or 99+99 in
CLIP mode.