EasyManua.ls Logo

Honeywell Notifier NFS-320 - Page 9

Honeywell Notifier NFS-320
42 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
NFS-320 and NFS-320SYS UL Listing Document — P/N 52745LD:G9 5/19/2022 9
Terminal Block/
Connector
Description Specifications
TB1 AC Power
Voltage and current:
NFS-320(SYS): 120 VAC 5.0 A
NFS-320E(SYSE): 240 VAC 2.5 A
Frequency: 50/60 Hz
Wiring size: Maximum 12 AWG (3.31 mm
2
) with 600 VAC insulation
Supervised
Non-power-limited
TB2 Power Auxiliary Outputs
Voltage: 24 VDC power at 0.5A
5 VDC power at 0.15A (See Note 1 and 10)
Power-limited (Class 2)
Maximum Ripple: 176 mVrms
Class B wiring. Supervise with a power supervision relay EOLR-1
Ground Fault Impedance: 0 ohms
Supervised
TB3 Battery Connection
Voltage: 24 VDC
Battery type: Sealed lead-acid
Maximum Battery Capacity: 200 AH
Non-power-limited
Over-current protected
Battery Charger Voltage: 27.6 VDC +/- 0.24 VDC
Battery Charger Current: 2.0 A or 5.7 A (Software selectable)
Supervised
Notes:
1. Total current drawn from the power supply by TB2, TB6 through TB9 and TB10 cannot exceed 3.0 A in standby or 6.0 A in an alarm
condition. The Control Panel provides a total of 4.4 A of power in standby and 7.4 A of power in alarm to be shared by all internal circuitry
and external provisions (24 V resettable and non-resettable).
2. NFPA 72 Local, Proprietary, and Central Station systems require 24 hours of standby power followed by 5 minutes in alarm.
3. NFPA 72 Auxiliary and Remote Station Systems require 24 hours of standby power followed by 5 minutes in alarm.
4. Batteries installed in a system powered by an automatic starting engine generator need to provide at least 4 hours of standby power.
5. Factory Mutual requires 90 hours of standby for deluge-preaction systems.
6. Emergency voice/alarm communications systems require 2 hours of operation in the alarm condition. Due to the sporadic nature of voice
operation, however, NFPA 72 permits 15 minutes of operation at a maximum connected load to equal 2 hours of normal use.
7. If the total exceeds 26 AH, the system requires a separate NFS-LBB, BB-100 or BB-200 battery enclosure for two larger capacity
batteries.
8. The following battery derating factors must be used for Canadian installations using NFS-320 charger:
• For a 26 AH battery, use derating factor of 1.5
• For a 55 AH battery, use derating factor of 1.8
• For a 100 AH battery, use derating factor of 2.5
• For a 200 AH battery, use derating factor of 2.5
• For 26 AH batteries: maximum standby current cannot exceed 0.65A; maximum alarm current cannot exceed 6.75A.
9. Internal Battery Charger on the CPS-24/E is rated for use with 18 AH to 200 AH batteries.
10. Accessories using the 5 VDC power connection must be located within 10 ft (3.658 m) of the FACP
11. UL2610 Proprietary Burg requires 24 hours of standby power
Table 2 NFS-320 Power Supply Wiring Connections

Other manuals for Honeywell Notifier NFS-320

Related product manuals