NFS2-3030 Listing Document — P/N LS10006-051NF-E:F2 5/19/2022 27
4 Programming Options and Menu Navigation
4.1 Programming Features Subject to AHJ Approval
This product incorporates field-programmable software. The features and/or options listed below must be approved by the local AHJ..
This product incorporates field-programmable software. In order for the product to comply with the requirements in the Standard for Control
Units and Accessories for Fire Alarm Systems, UL 864/ULC-S527, certain programming features or options must be limited to specific values
or not used at all as indicated below.
Program Feature or Option
Permitted
in UL 864?
(Y/N)
Permitted
in UL 2610
(Y/N)
Permitted in
ULC-S527
(Y/N)
Possible Settings
Settings
Permitted in
UL 864
Settings
Permitted
in UL 2610
Settings
Permitted in
ULC-S527
IP downloads over a local area
network (LAN) or the internet
(Wide Area Network - WAN)
No N/A No Yes
No
Timed
No N/A No
Releasing: Abort Switch Yes N/A Yes NYC
AHJ
ULI
IRI
ULI
IRI
N/A ULI
IRI
Detector Programming:
Supervisory Type Codes
Yes N/A Yes SUP L(DUCTI)
SUP T(DUCTI)
SUP T(DUCTP)
SUP L(DUCTP)
SUP L(ION)
SUP T(ION)
SUP L(PHOTO)
SUP T(PHOTO)
SUP L(LASER)
SUP T(LASER)
F/CO (P SUP)
SUP L(DUCTI)
SUP T(DUCTI)
SUP L(DUCTP)
SUP T(DUCTP)
N/A SUP
L(DUCTI)
SUP
T(DUCTI)
SUP
L(DUCTP)
SUP
T(DUCTP)
AC Fail Delay Timer Yes N/A Yes None, or 1-12
hours
1-3 hours N/A 1-3 hours
Regional Settings Yes N/A Yes Singapore
Chicago
Australia
China
Canada
Korea
Chicago N/A Canada
DCC Enable Yes N/A Yes Enable/Disable Enable/Disable N/A Enabled
FMM-4-20 Event Settings Yes N/A Yes No Event
Trouble
Fire
Supervisory
Security
Nonfire
Critical Process
No Event
Trouble
Supervisory
Security
Nonfire
Critical Process
N/A No Event
Trouble
Supervisory
Security
Nonfire
Critical
Process
Alarm Verification Time Yes N/A Yes 0 to 240 seconds 0 to 60 seconds N/A 0 to 60
seconds
Trouble reminder Duration:
Wireless Applications
Yes N/A Yes 4 Hours
24 Hours
4 Hours N/A 4 Hours
Alarm Reminder Yes N/A Yes 24 Hours
Off
24 Hours N/A 24 Hours
Supervisory Reminder Yes N/A Yes 24 Hours
Off
24 Hours N/A 24 Hours
CO Reminder Yes N/A Yes 24 Hours
Off
24 Hours N/A 24 Hours
Presignal Delay/PAS
1
Yes N/A No Presignal Delay:
60-180 seconds
PAS (Positive
Alarm
Sequence):15
seconds
Yes N/A No
Exit Time Dealy N/A Y N/A N/A N/A
60 Sec. or
Less
N/A
Entry Time Delay N/A Y N/A N/A N/A
60 Sec. or
Less
N/A