12 NFS2-640 UL Listing Document — P/N 52741LD:H9 5/19/2022
Connecting an RKS-S Remote Key Switch
The RKS-S Remote Key Switch arms and disarms the system. It can be mounted in a UL listed single-gang electrical box. Both the monitor module
and RKS-S must be mounted within the protected area. Refer to the Product Installation Document (15984) for information on how to wire the RKS-S
to a FMM-1 and FMM-101 module.
Single Tenant Security System with Entry/Exit Delay
The following system requirements are illustrated in Figure 14 on page 12.
• One NFS2-3030 Control Panel
• Multiple Security Supervisory Circuits Reporting to Central Station as a Single Area
• The minimum security equipment required is as follows:
– Multiple MM Monitor Modules per Protected Area
– One Group Interface for security alarm
– One Group Interface to generate trouble arming system
– Contact Switch for Each Entry/Exit Door
– RKS-S Key Switch
– MM Monitor Modules
– Remote Annunciator for Each Entry/Exit Door (ACM-24AT, ACM-48A, ACM-16AT, ACM-32A)
– Security Devices
– RM Relay Module
– Compatible Printer
Programming of Key Switch, Access Points, and Motion Detection
RKS Remote Key Switch with Monitor Module
Address: LXXMYYY (arbitrary)
Type ID: ACCESS MONITOR
Zone Map: (none)
Custom Label: Arming Switch
Contact Switches with Monitor Modules
Address: LXXMYYY (arbitrary)
Type ID: ACCESS MONITOR
TENANT A
AREA 1
(Perimeter
and interior)
To Signaling
Line Circuit
MM
To Central Station
(via EIA-485 circuit)
Entry/Exit Door
NFS2-3030 Central Station
* Gr
oup Interface must
be
physically located in either
the pr
otected premises or
the Central Station
Key
Motion Detector
Contact Switch
Contact Switch with MM Module
Pull Station
Smoke Detector
RKS-S Remote Key Switch with MM Module
Remote Annunciator
MM Security Access Monitor
Group Interface *
RM
MM RM
Figure 14 Single Tenant Security System with Entry/Exit Delay
Compatible Printer