NFS2-640 Operations P/N 52743:L4 06/10/19 67
Appendix C: Remote Terminal Access
C.1 General Description
The control panel can communicate with a remote terminal or computer connected to the EIA-232
PC/Terminal port. Refer to the NFS2-640 Installation Manual for installation information.
This port may be set up for interactive operation or for monitoring only. Interactive operation
requires that all equipment be UL-listed under UL Standard for Safety UL 864 and be installed and
set up as directed under Local Terminal Mode (LocT) or Local Monitor Mode (LocM).
ITE (Information Technology Equipment) equipment listed under UL 1950 is allowed for ancillary
system monitoring when the system is installed and set up as directed under Remote Terminal
Mode (RemT).
C.2 Operating Modes
The control panel provides three operating modes for the CPU EIA-232 PC/Terminal port:
Local Terminal - LocT
Local Monitor - LocM
Remote Monitor - RemM
You select the operating mode during control panel programming (Global System Functions). For
more information, refer to the NFS2-640 Programming Manual.
The following subsections outline the functions, password requirements, and additional informa-
tion for each operating mode.
C.2.1 Local Terminal Mode (LocT)
Functions, passwords, and special requirements of Local Terminal Mode (LocT) are:
Functions available with the Local Terminal Mode:
NOTE: See the NFS2-640 Programming Manual for instructions on enabling the CRT.
Functions: Read Status, Alter Status, and Control Functions (Table C.1).
Passwords: User-defined password for Alter Status functions.
Requirements: The terminal must be mounted in a UL 864 listed enclosure or positioned to provide
equivalent protection against unauthorized use.
Function Lets you...
Read Status
Display the status of an individual point (Detector, Module, or Zone).
Display a list of all the points in Alarm or trouble.
Display a list of all programmed points in the system.
Step through the History buffer event by event.
Display the entire History buffer.
Step through Alarm History
Display the entire Alarm History
Alter Status
Disable/Enable an individual point.
Change the sensitivity of a detector.
Clear the verification counter of all detectors.
Clear the entire History buffer.
Set the Intelligent Sensing alert and action levels.
Table C.1 Local Terminal Mode Functions (1 of 2)

Other manuals for Honeywell Notifier NFS2-640

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell Notifier NFS2-640 and is the answer not in the manual?

Honeywell Notifier NFS2-640 Specifications

General IconGeneral
BrandHoneywell
ModelNotifier NFS2-640
CategoryControl Panel
LanguageEnglish

Related product manuals