NFW-100X Manual — P/N LS10131-001NF-E:C 7/25/2018 137
Appendix B: Default Programming
The following table provides a list of the programming options and their factory default settings.
Program Option Factory Default Program Option Factory Default
Detector Programming Not Installed Aux Power Class A No
Detector Type Smoke-Photo Aux Power Resettable No
Detector Verification Off Aux Power 2 Resettable No
Detector Walktest Yes Canadian Option Enabled No
Detector PAS No Waterflow Silenceable No
Detector Presignal No Relay 1 Alarm
Detector Zone Assign. 000 only Relay 2 Trouble (fixed)
Detector Adj/Noun none Relay 3 Supervisory
Module Programming Not Installed Communicator Installed Yes
Module Type Monitor POTS, Ethernet, Cellular Enabled No
Module Walktest Yes Ethernet, Cellular Location ID 0000
Module Presignal No Ethernet, Cellular CS ID 0000
Module Zone Assign. 000 only POTS, Ethernet, Cellular Account Code 000000
Module Adj/Noun none POTS Enabled No
Module Control Module Delay No POTS Type Touchtone
Module MNS Override No POTS Supervised No
Message No Message Gains Dialing Normal
Zone Type Alarm Zone Gains Reporting Normal
Zone 000 Enable Enabled IP Settings- DHCP Enabled
Zone 001 Enable Enabled Trouble Report Limit 0
Zone 002 Enable Enabled Report Style Point
Zone 003 Enable Enabled AC Loss Delay 2
.........................through.......... ..................... Primary Account Code 000000
Zone 095 Enable Enabled Secondary Account Code 000000
Special Purpose Zones 096-099 Off Test Time 0100
Loop Class Class B Primary Phone Number
Loop Protocol LITESPEED Secondary Phone Number
Trouble Reminder 24 Hr Primary Comm Format Ademco Contact ID
Banner Secondary Comm Format Ademco Contact ID
Time Format 12 Hr ANN-Primary Enabled No
Hours Setting 12 ANN-Primary Modules Addr. 1 - 8 None
Minutes Setting 00 ANN-Secondary Enabled No
Second Settings 00 ANN-Secondary Modules Addr. 1 - 8 None
AM-PM Setting AM ANN-S/PG Port Serial
Month Setting 01 ANN-S/PG Baud 9600
Day Setting 01 ANN-S/PG Data Bits 7
Year Setting 00 ANN-S/PG Parity Even
Daylight Savings Enabled ANN-S/PG Stop Bits 1
Month Start Daylight Savings April ANN-S/PG Offline Timer 60
Week Start Daylight Savings Week 2 ANN-S/PG Printer Supervision No
Month End Daylight Savings November ANN-80/100 Piezo Enabled Yes
Week End Daylight Savings Week 1 ANN-80/100 Lock Enabled Yes
Alarm Verification Off ANN-80/100 Acknowledge Button Enabled Yes
PAS Timer 0 ANN-80/100 Silence Button Enabled Yes
Presignal Timer 0 ANN-80/100 Reset Button Enabled Yes
Waterflow Retard Timer 0 ANN-80/100 Drill Button Enabled Yes
Control Module Delay Timer 0 ANN-I/O Point/Zone Zone
NAC 1,2,3, & 4 Enable Enabled ANN-I/O Range 00-29
NAC 1,2,3, & 4 Silenceable Yes ANN-I/O Active LEDs Only
NAC 1,2,3, & 4Type Strobe Sync ANN-RLY Relay 1 Zone 1
NAC 1,2,3, & 4 Sync Type System Sensor ................through....................... ............
NAC 1,2,3, & 4 Autosilence 0 ANN-RLY Relay 10 Zone 10
NAC 1,2,3, & 4 Coding Steady ANN-LED Point/Zone Zone
NAC 1,2,3, & 4 Zones Zone 000 only ANN-LED Alarms/ATS (Alarm, Trbl, Supv) ATS
NAC 1,2,3, & 4 Silence Inhibit No ANN-LED Range 0 - 9
MNS Active No F1 - F4 function keys Disabled
Charger Enabled Yes Master Password 00000000
4XTM Supervision No Maintenance Password 11111111
Remote Sync Enabled Yes Upload/Download Password 22222222