Programming Master Programming Level
Select the desired output. The following screen will be displayed.
Each output can be programmed as resettable or non-resettable power. Non-resettable power is suitable for powering annunciators while
resettable power is suitable for powering smoke detectors. Each press of the 2 key will cause the display to toggle between Resettable
Yes and Resettable No.
In addition, Aux 1 can be programmed for Class A wiring. If Aux 1 is to be wired for Class A, press 1. Each press of the 1 key will cause
the display to toggle between Class A Yes and Class A No.
Trouble Reminder
The Trouble Reminder features causes the control panel piezo to sound a reminder ‘beep’ for alarms and
troubles, after the panel has been silenced. Refer to “Trouble Reminder” on page 71, for a detailed descrip-
tion of this feature. Pressing 2 while viewing System Setup Screen #4 will cause the display to toggle to
Trouble Rem 4 or Trouble Rem 24, which enables this feature for resound at either 4 or 24 hours, respec-
tively. Each press of the 1 key will cause the display to toggle between Trouble Rem 4 or Trouble Rem 24.
Refer to the table on page 49 for permissible settings.
Language
The language option is used to change the text on the panel display to either English or French. Pressing the
3 key will cause the display to offer a choice of 1=English and 2=French.
Charger Enable
If using an external battery charger, the FACP battery charger must first be disabled. Pressing 1 while view-
ing System Setup Screen #5 will cause the display to toggle to Charger Enab No, which will allow the use
of an external battery charger. Each press of the 1 key will cause the display to toggle between Charger
Enab Yes and Charger Enab No.
4XTM Supervision
If a 4XTM Transmitter Module is installed in the system, supervision must enabled in user programming.
Pressing 2 while viewing System Setup Screen #5 will cause the display to toggle to 4XTM Supv Enab. Yes,
which means there is a 4XTM installed. Each press of the 1 key will cause the display to toggle between
4XTM Supv Enab. No and 4XTM Supv Enab. Yes. Refer to the table on page 49 for permissible settings.
Remote Sync Enable
Synchronization is a feature that controls the activation of notification appliances in such a way that all
devices will turn on and off at exactly the same time. Refer to Section 2.5, “Remote Synchronization Out-
put”, on page 28 for more information. To enable remote synchronization, press the 3 key while viewing
System Setup Screen #5. Each press of the key will toggle the screen between Rem Sync Enab Yes and Rem
Sync Enab No.
3.6.6 History
The History option allows an authorized user to view or erase events which have occurred in the control
panel. Pressing 1 while viewing Programming Screen #3 will display the History options as shown in the
following display:
AUX 1
1=CLASS A YES
2=RESETTABLE YES
SYSTEM SETUP
1=AUX POWER
2=TROUBLE REM 24HR
System Setup Screen #4
SYSTEM SETUP
1=AUX POWER
2=TROUBLE REM 24HR
3=LANGUAGE ENGLISH
System Setup Screen #4
SYSTEM SETUP
1=CHARGER ENAB YES
2=4XTM SPV ENAB NO
3=REM SYNC ENAB YES
System Setup Screen #5
SYSTEM SETUP
1=CHARGER ENAB YES
2=4XTM SPV ENAB NO
3=REM SYNC ENAB YES
System Setup Screen #5
SYSTEM SETUP
1=CHARGER ENAB YES
2=4XTM SPV ENAB NO
3=REM SYNC ENAB YES
System Setup Screen #5
PROGRAMMING
1=HISTORY
2=COMMUNICATOR
3=ANNUNCIATORS
Programming Screen #3
HISTORY
1=VIEW EVENTS
2=ERASE HISTORY
History Screen