72 NFW-100X Manual — P/N LS10131-001NF-E:C 7/25/2018
Programming Master Programming Level
Remote Sync Enable: This feature controls the activation of notification appliances in such a way that all devices will turn on and
off at exactly the same time.
Pressing 2 for System Setup, while viewing Programming Screen #2, will cause the following screens to be
displayed:
Function Keys
The NFW-100X keypad has 4 programmable function keys. These keys can be programmed to allow rapid disable/enable of various fire
panel inputs and outputs during scheduled maintenance. pressing any function key results in a trouble signal at the panel. Pressing 1 on
System Setup Screen #1 displays the following:
Select 1, 2, 3, or 4 to program the corresponding Function Key. The following screens display for each
Function Key where “(X)” represents the number of the key chosen.
To Enable or Disable the Function Key, press the 1 key while viewing the Function Keys Screen #1. Each press of the key will toggle the
screen between Key Enabled Yes and Key Enabled No.
Pressing 2 key while viewing the Function Keys Screen #1 allows the user to select individual zones that the Function Key will control.
Pressing 3 assigns all zones to the selected Function Key.
Each function key can be assigned to control any of the 4 onboard NAC circuits on the NFW-100X. By pressing the 2 key while viewing
the Function Keys Screen #2 the following screen displays, allowing the user to select the desired NAC circuit(s).
Pressing 1, 2, 3, or 4 toggles the screen between Yes (controlled by function key) and No (not controlled by function key) for each
onboard NAC circuit.
The Remote Synchronization (TB8 on the FACP’s main circuit board) can also be disabled through pro-
gramming of a function key. To disable remote synchronization, press the 3 key while viewing the Function
Keys Screen #2. Each press of the key will toggle the screen between Rem Sync Disb Yes and Rem Sync
Disb No.
Banner
The top line of the display, which appears when the control panel is in normal mode, can be changed by
using the Banner option. Pressing 2 while viewing System Setup Screen #1 will cause the following to be
displayed:
PROGRAMMING
1=LOOP SETUP
2=SYSTEM SETUP
3=FUTURE USE
Programming Screen #2
SYSTEM SETUP
1=FUNCTION KEYS
2=BANNER
3=TIME-DATE
System Setup Screen #1
SYSTEM SETUP
1=TIMERS
2=NAC
3=RELAYS
System Setup Screen #2
SYSTEM SETUP
1=CANADIAN OPT. OFF
2=WATERFLOW SIL. NO
3=MNS OVERRIDE NO
System Setup Screen #3
SYSTEM SETUP
1=AUX POWER
2=TROUBLE REM 24HR
3=LANGUAGE ENGLISH
System Setup Screen #4
SYSTEM SETUP
1=CHARGER ENAB YES
2=4XTM SPV ENAB NO
3=REM SYNC ENAB YES
System Setup Screen #5
FUNCTION KEYS
1=F1 3=F3
2=F2 4=F4
Function Keys Screen
FUNCTION KEYS
1=F1 3=F3
2=F2 4=F4
Function Keys Screen
Function Keys Screen #1
Function Keys Screen #2
F(X) KEY OPERATION
1=KEY ENABLED NO
2=ZONES
3=ALL ZONES
F(X) KEY OPERATION
1=NACS
2=REM SYNC DISB NO
F(X) NACS
1=NAC 1 Y 3=NAC 3 N
2=NAC 2 Y 4=NAC 4 N
Function Keys Screen
F(X) KEY OPERATION
1=NACS
2=REM SYNC DISB YES
Function Keys Screen #2
SYSTEM SETUP
1=FUNCTION KEYS
2=BANNER
3=TIME-DATE
System Setup Screen #1
BANNER
1=FACTORY
2=USER DEFINED
Banner Screen