NFW-100X Manual — P/N LS10131-001NF-E:C 7/25/2018 81
Master Programming Level Programming
View Events
Pressing 1 while viewing the History Screen will allow the user to select the events to be viewed as illus-
trated in the following:
While displaying the View Events screen, press 1 to view all events, 2 to view only alarms or 3 to view other events. Use the up and
down arrow keys to scroll through all of the displayed events.
Erase History
The Erase History option allows a user to erase all events from the history file. This will provide a clean slate in order to use the history
file to track future events. Pressing 2 while viewing the History Screen will display the following screen:
Pressing 1 while viewing the Erase History Screen will erase all events from the History file. During this process, the display will read as
follows:
After the History file has been erased, the display will return to the History Screen.
3.6.7 Communicator
The communicator settings allow the user to configure the settings for the pre-installed IPOTS-COM and
CELL-MOD/CELL-CAB-N if installed in the system. Pressing 2 while viewing the Programming Screen
#3 will cause the following Communicator options to be displayed:
Communicator Installed
The pre-installed communicator provides communication to a central station. Use of the communicator requires it be enabled in user pro-
gramming.Pressing 1 while viewing the Communicator Screen #1 will change the display to Installed No. Each press of the 1 key will
cause the display to toggle between Installed Yes and Installed No.
POTS Settings
The POTS settings configure the system when telephone lines are used to contact central station. Pressing 2
while viewing the Communicator Screen #1 will display the following.
HISTORY
1=VIEW EVENTS
2=ERASE HISTORY
History Screen
HISTORY
1=VIEW ALL
2=VIEW ALARMS
3=VIEW OTHER EVENTS
View Events Screen
ERASE HISTORY
PROCEED ?
1=YES 2=NO
Erase History Screen
ERASING HISTORY
PLEASE WAIT
Erase History Wait Screen
PROGRAMMING
1=HISTORY
2=COMMUNICATOR
3=ANNUNCIATORS
Programming Screen #3
COMMUNICATOR
1=PRI COMM PATH
2=SEC COMM PATH
3=TBL REPRT LIMIT 0
Communicator Screen #2
COMMUNICATOR
1=INSTALLED YES
2=POTS SETTINGS
3=IP SETTINGS
Communicator Screen #1
COMMUNICATOR
1=REPORT SYTLE POINT
2=EVENT CODES
Communicator Screen #3
COMMUNICATOR
1=INSTALLED YES
2=POTS SETTINGS
3=IP SETTINGS
Communicator Screen #1
POTS SETTINGS
1=LINE 1
2=LINE 2
3=GAINS
POTS Settings Screen