NFW-100X Manual — P/N LS10131-001NF-E:C 7/25/2018 15
Specifications Product Description
Remote Sync Output - TB8
Remote power supply synchronization output
24 VDC nominal special application power
Maximum current is 350 mA
End-of-Line Resistor: 4.7KΩ
Output linked to NAC 1 control
Supervised and power-limited circuit
Programmable Class A or Class B wiring
Secondary ANN-BUS - TB10
ANN-BUS annunciator connector, Terminal 1 (+/A) and Terminal 2 (-/B)
Annunciators require non-resettable power
Primary ANN-BUS - TB9
Class A or Class B wiring
ANN-BUS annunciator connector, Terminal 1 (+/A) and Terminal 2 (-/B)
Class A wiring uses Terminal 3 (+/A Return) and Terminal 4 (-/B Return)
Annunciators require non-resettable power
The following figure illustrates the maximum current that is possible for each major panel output circuit and the total current available
from the FACP.
TB5
TB6
TB7
TB8
5
6
Figure 1.1 Current Availability without PWRMOD24 Option
Refer to the battery calculations section for additional information.
Standby
2.0 amps max
per panel
Special Application
Nonresettable or
Resettable Power
Special Application
Resettable or
Nonresettable Power
NAC #1
NAC #2
NAC #3
NAC #4
1.0 amp max
per circuit
2.5 amps max
per circuit
Alarm
3.0 amps max*
per panel
Remote
Synchronization
Output
*Note: When the option module
PWRMOD24 is installed, an
additional 3.0 amps of alarm power is
available across NAC #1 through
NAC #4 and the remote
synchronization output expanding
max power to 6.0 amps
1.0 amp max
per circuit
2.5 amps max
per circuit
2.5 amps max
per circuit
2.5 amps max
per circuit
0.35 amp max
per circuit