76 NFW-100X Manual — P/N LS10131-001NF-E:C 7/25/2018
Programming Master Programming Level
The Notification Appliance Circuits can be configured independently by pressing 1 for NAC 1, 2 for NAC 2, 3 for NAC 3, or 4 for NAC
4.
The following screens will be displayed for each selection:
Enabled
Pressing 1 while viewing NAC Screen #1 will cause the display to change to Enabled No. This will prevent the selected main circuit
board NAC from activating its devices. Each press of the 1 key will cause the display to toggle between Enabled Yes and Enabled No.
Type
The main circuit board NAC type can be programmed by pressing 2 while viewing NAC Screen #1. The
following screen will be displayed. Press the down arrow key to view additional screens:
Select the NAC device type by pressing the number corresponding to the type in the appropriate screen. When the selection is made, the
display will return to NAC Screen #1.
The following table contains NAC type codes and their functions:
Silenceable
Pressing 3 while viewing NAC Screen #1 will cause the display to change to Silenceable No. This will prevent the selected main circuit
board NAC from being silenced by pressing the Alarm Silence key or by the Auto Silence feature. Each press of the 3 key will cause the
display to toggle between Silenceable Yes and Silenceable No.
Important: When a Notification Appliance Circuit with a mix of audible and visual devices is programmed for silenceable and the
Synced Strobe feature is selected, only the audible devices will be turned off if the Silence key is pressed or if the Autosilence feature is
enabled. The visual devices (strobes, etc.) will continue to operate. If the Strobe Sil Sync feature is selected, Silence or Autosilence will
turn off both audible and visual devices.
Auto Silence
The Auto Silence feature, when enabled, automatically silences all main circuit board silenceable notifica-
tion appliances after a programmed length of time. To enable this feature and program the time delay before
Auto Silence activation, press 1 while viewing NAC Screen #2. The following screens will be displayed:
NAC #
1=ENABLED YES
2=TYPE SYNCED STROBE
3=SILENCEABLE YES
NAC Screen #1
NAC #
1=ZONE ASSIGNMENT
000 000 000 000 000
2=SILENC INHIBIT NO
NAC Screen #2
NAC #
1=AUTO SILENCE 00
2=CODING TEMPORAL
NAC Screen #3
NAC #
1=SYNC TYPE S
2=MNS OVERRIDE NO
3=MNS ACTIVE NO
NAC Screen #4
NOTE:
The programming for NAC 1 will determine the operation of the remote power supply sync.
NAC Type Code Special Function
Bell None
Horn None
Strobe None
Synced Strobe Synchronized to manufacturer
Strobe Sil Sync Same as Synced Strobe but Silence turns off audible & visual devices
Future Use None
Future Use None
Future Use None
Blank None
NAC #
1=ENABLED
2=TYPE
3=SILENCEABLE
NAC Screen #1
NAC TYPE
1=BELL
2=HORN
3=STROBE
Type Screen #1
NAC #
1=AUTO SILENCE
2=CODING TEMPORAL
NAC Screen #2
AUTO SILENCE
1=NO
2=5 MINUTES
3=10 MINUTES
Auto Silence Screen #1
AUTO SILENCE
1=30 MINUTES
Auto Silence Screen #2
AUTO SILENCE
1=15 MINUTES
2=20 MINUTES
3=25 MINUTES
Auto Silence Screen #3