88 NFW-100X Manual — P/N LS10131-001NF-E:C 7/25/2018
Programming Master Programming Level
DUCT SUPERVISORY 200 Zone Point FS FV
DET-USER-DEF-7 200 Zone Point FS FV
PHOTO SUPER AR 200 Zone Point FS FV
DET-USER-DEF-8 111 Zone Point FA FH
CO SUPERVISORY 200 Zone Point GS GV
DET-USER-DEF-9 111 Zone Point FA FH
PHOTO ADAPT 111 Zone Point FA FH
DET-USER-DEF-10 111 Zone Point FA FH
PHOTO BEAM 111 Zone Point FA FH
DET-USER-DEF-11 111 Zone Point FA FH
MONITOR 110 Zone Point FA FH
MON-USER-DEF-3 110 Zone Point FA FH
SMOKE CONVEN 111 Zone Point FA FH
MON-USER-DEF-5 111 Zone Point FA FH
HEAT CONVENTIONAL 114 Zone Point KA KH
MON-USER-DEF-6 114 Zone Point KA KH
MEDIC ALERT 100 Zone Point MA MH
MON-USER-DEF-7 100 Zone Point MA MH
HAZARD ALERT 150 Zone Point PA PH
MON-USER-DEF-8 150 Zone Point PA PH
TORNADO ALRT 150 Zone Point PA PH
MON-USER-DEF-9 150 Zone Point PA PH
TAMPER 144 Zone Point TA TH
MON-USER-DEF-11 144 Zone Point TA TH
MON SUPERVISORY 200 Zone Point FS FV
MON-USER-DEF-12 200 Zone Point FS FV
MON SUPERV AUTO 200 Zone Point FS FV
MON-USER-DEF-13 200 Zone Point FS FV
HVAC OVRRIDE 200 Zone Point FS FV
POWER MON 330 Zone Point AT AR
MON-USER-DEF-14 330 Zone Point AT AR
TROUBLE MON POINT_FAULT code will
always
be transmitted
MON-USER-DEF-15 POINT_FAULT code will
always
be transmitted
PROCESS MON 000 Zone Point 00 00
MON-USER-DEF-16 000 Zone Point 00 00
PROC MON AR 000 Zone Point 00 00
MON-USER-DEF-17 000 Zone Point 00 00
MON-USER-DEF-18 000 Zone Point 00 00
POINT FAULT 380 Zone Point FT FJ
POINT DISABLE 570 Zone Point FB FU
MNS EVENT 580 000 000 00 00
MNS OVERRIDE 581 000 000 00 00
MNS MESSAGE 000 000 Message # 00 00
MANUAL EVACUATION 110 000 000 00 00
AC_FAIL 301 000 000 AT AR
DRILL 604 000 000 FI FK
SLC 1 SHORT A 372 000 000 ET ER
SLC 1 SHORT B 372 000 000 ET ER
SLC 1 OPEN A 371 000 000 ET ER
SLC 1 OPEN B 371 000 000 ET ER
SLC 1 GND FAULT POS 310 000 000 ET ER
Table 3.3 Event Codes (Continued)