EasyManuals Logo

Honeywell NOTIFIER SCS Series User Manual

Honeywell NOTIFIER SCS Series
210 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #31 background imageLoading...
Page #31 background image
SCS Series Manual — P/N 15712:L 7/18/16 31
Basic Smoke Control System Operation Concepts of Smoke Control
These steps would be accomplished as follows:
1. Turn ON the stairtower and elevator hoistway fans.
2. CLOSE return dampers for all nonsmoke zones. As an example, if the fire event occured on floor 5, the areas specific to this example
would be floors 1-4 and floors 6-8. This step would involve the closing of 14 dampers.
3. CLOSE supply dampers for the smoke zone (floor 5). This step would involve the closing of 2 dampers.
4. Turn ON both the supply fan and the return fan.
At this point the smoke control system would be fully operational. Section 3 “The SCSSCE” gives specific information on accomplishing
these steps with the SCS-8SCE-8 and associated equipment.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell NOTIFIER SCS Series and is the answer not in the manual?

Honeywell NOTIFIER SCS Series Specifications

General IconGeneral
BrandHoneywell
ModelNOTIFIER SCS Series
CategoryControl Unit
LanguageEnglish

Related product manuals