EasyManuals Logo
Home>Honeywell>Control Unit>NOTIFIER SCS Series

Honeywell NOTIFIER SCS Series User Manual

Honeywell NOTIFIER SCS Series
210 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #44 background imageLoading...
Page #44 background image
44 SCS Series Manual — P/N 15712:L 7/18/16
The SCSSCE SCS-8SCE-8 Installation
Wiring Specifications
The EIA-485 circuit cannot be T-Tapped; it must be wired in a continuous fashion from the control panel to
the SCS-8. The maximum wiring distance between the panel and the last SCS-8 or annunciator is 6,000 feet
@ 16 AWG. All SCS-8/ SCE-8 modules must be contained in the same room with the FACP/INA/NCA in
FSCS mode. The wiring size must be a 12 to 18 AWG twisted pair cable having a Characteristic Impedance
of 120 ohms, +/- 20% (shielded cable is recommended). Limit the total wire resistance to 100 ohms on the EIA-485 circuit, and 10 ohms on
the SCS-8 power circuit. Do not run cable adjacent to, or in the same conduit as, 120 volts AC service, noisy electrical circuits that are pow-
ering mechanical bells or horns, audio circuits above 25 volts (RMS), motor control circuits, or SCR power circuits.
Terminal Wiring
The following should be considered when connecting terminal wiring:
Do not “T-Tap” the EIA-485 circuit. It will not function properly. Wire it as shown in Figure 3.14.
AM2020/AFP-1010/INA - Install the built-in 120 ohm resistor on the SCS-8 module if it is located at the physical end of the EIA-485
circuit, by turning ON dipswitch 8 on the SCS-8. Turn OFF dipswitch 8 on all other SCS-8 modules. If an EIA-485 device other than an
SCS-8SCE-8 is at the physical end of the EIA-485 loop, install a R-120 resistor across the EIA-485 out terminals of the device and
ensure that dipswitch 8 is turned OFF on all SCS-8 modules.
Connect Earth Ground to a mounting screw on the backbox or cabinet.
Connect 24 VDC Power to the SCS-8. This power need not be supervised by a power supervision relay since it is inherently supervised
by the control panel (loss of communications is registered during loss of power to the SCS-8).
When the EIA-485 shield is in conduit: Connect it to the system reference (system common). The shield can enter the cabinet, but must be
insulated from the cabinet (no electrical contact). Between Smoke Control Stations, wire-nut multiple shields together and insulate. Treat the
shield like a system wire making certain it does not come in contact with other wires or earth ground.
When the EIA-485 shield is not in conduit: Terminate the shield at the outside of the FACP backbox (ground). Do not allow the shield to
enter or even touch the cabinet. Between Smoke Control Stations, wire-nut multiple shields together outside of the respective enclosures.
Enclosure
SCS-8
Terminal
Block
Figure 3.12 Terminating the Shield
NOTE: All enclosures, including the FACP backbox, must be connected to earth ground! Never use the shield for grounding purposes.
Terminate the EIA-485 shield at the Fire Alarm Control Panel only.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell NOTIFIER SCS Series and is the answer not in the manual?

Honeywell NOTIFIER SCS Series Specifications

General IconGeneral
BrandHoneywell
ModelNOTIFIER SCS Series
CategoryControl Unit
LanguageEnglish

Related product manuals