3
PAK200467-HW_01A March 2020 2020 Honeywell Security
Model Specification Table
PS-HL-13805BM-4OP
PS-HL-13810BM-8OP
Max Output Current to load
5A
2 x 5A
Output Fuses* (20mm glass)
F5.0A (4 x 1.25A)
2 x F5.0A (8 x 1.25A)
Max Mains Input Current (at
90V ac)
2.0A
3.0A
Mains Input Fuse
(20mm 250Vac HBC)
T3.15A
T3.15A
Battery Fuse Protection
F5.0 A
2 x F5.0A
LOCAL INDICATORS
Local Indicators
MAINS LED (Green)
Mains present
FAULT LED (Red)*
Flashes (1s period) when: loss of mains, battery
disconnected, output fuse fail, battery fuse fail, output
short circuit or low output voltage
*For 10A model, only one Fault LED will be visible via front panel. Each module has
independent fault monitoring and signalling.