10 PW-7000 Two-Reader Module Installation Guide, Document 800-25676V1
Specifications
The Two-Reader Module is for use in low voltage, class 2 circuits only.
Primary power:
• 12VDC + 10%, 650mA maximum with 5V readers, 300 mA max. excluding
readers
Relay contacts:
• Relays 0 and 2 outputs, Form-C, 5A @ 30VDC, resistive
• Relays 1, 3, 4, and 5 outputs, Form-C, 2A @ 30VDC, resistive
Inputs:
• 8 supervised, End of Line resistors 1k ohm ± 1% tolerance
• 2 unsupervised dedicated inputs
Reader interface:
Communication:
Wire requirements:
Mechanical:
Environment:
Reader power
5VDC(5 - 6.2) 300mA max. each or 12VDC (pass-through),
300mA max. each
Reader LED output
TTL compatible, high > 3V, low < 0.5V, 5mA source/sink max.
Reader buzzer output
Open collector, 5VDC open circuit max. 10mA sink max.
Reader data inputs
TTL compatible inputs
RS-485
9,600 to 38,400 bps
Power
1 twisted pair, 18AWG
RS-485
24AWG, 4,000 feet (1,200 m) max., 2-twisted pair with shield
(120 ohms, 23pf) (Belden 9842 or equiv.)
Inputs
1 twisted pair per input, 30 ohms max.
Outputs
As required for the load
Readers
6 conductors, 18AWG, 500 feet (150m) max. shield and drain
Dimension
5.5" (140mm) W x 9" (229mm) L x 1" (25mm) H
Weight
12 oz. (340g) nominal
Temperature
0°C to +49°C, operating, -55°C to +85°C, storage
Humidity
0% to 85% RHNC