S9361A207X INTEGRATED BOILER CONTROLLERS
69-2751—05 6
WIRING
Electrical Shock Hazard.
Can cause severe injury, death or property 
damage.
Disconnect the power supply before making 
wiring connections to prevent electrical shock 
or equipment damage.
Check the wiring diagram furnished by the appliance 
manufacturer for circuits differing from the wiring 
hookup shown in Fig. 4. Carefully follow any special 
instructions affecting the general procedures outlined 
below.
IMPORTANT
1. All wiring must comply with applicable local 
electrical codes and ordinances.
2. A common ground is required for the S93XX 
and the main burner. The 24V “secondary” 
plug internally grounds one side of the trans-
former. Any auxiliary controls or limits must 
not be in the grounded leg. In addition, the 
appliance should be earth-grounded.
3. Make sure the transformer has adequate VA. 
The ignition module requires at least 0.2A at 
24 Vac. Add the current draws of all other 
devices in the control circuit, including the gas 
control, and multiply by 24 to determine the 
total VA requirements of these components. 
Add this total to 5.0 VA (for the module). The 
result is the minimum transformer VA rating. 
Use a Class II transformer if replacement is 
required.
4. Check that L1 (hot) and L2 (neutral) are wired 
to the proper terminals.
Connect Ignition Cable (S936XAXXXX)
Use Honeywell ignition cable or construct an ignition 
cable that conforms to suitable national standards, 
such as Underwriters Laboratories Inc. See 
Specifications section. To construct a cable, fit one 
end (the module end) with 1/4 in. connector 
receptacle and the other with a connector to match 
the pilot assembly. Protect both ends with insulated 
boots.
NOTE: Cable length must be 36 in. (0.9 m) or less. 
The cable must not be in continuous contact 
with a metal surface or spark voltage will be 
greatly reduced. Use ceramic or plastic 
standoff insulators as required.
1. Connect one end of the cable to the male 
quick-connect SPARK terminal on the module.
2. Connect the other end of the cable to the igniter 
or igniter-sensor stud on the pilot 
burner/igniter-sensor.
Connect Vent Damper (Vent Damper 
Models)
A vent damper can be used with modules provided 
with a vent damper plug connector. The Molex
®
 plug 
provided simplifies wiring connections.
To connect the vent damper, follow the wiring 
diagrams supplied with the vent damper for typical 
connections.
Connect Remaining Module 
Connectors
Connect remaining system components to the 
ignition module terminals as shown in the appropriate 
wiring diagrams, Fig. 4.
Connect Gas Control
Use No. 18 AWG or larger, depending on estimated 
curret draw, solid or stranded wire. Connect to gas 
control terminals as shown in wiring diagrams, using 
terminals appropriate to the gas control.
Ground Control System
The igniter/flame sensor and module must share a 
common ground with the main burner. Use AWM 
insulated wire with a minimum rating of 105°C 
(221°F) for the ground wire; asbestos insulation is not 
acceptable. If necessary, use a shield to protect the 
wire from radiant heat generated by the burner.
The burner serves as the common grounding area. If 
there is not a good metal-to-metal contact between 
the burner and ground, run a lead from the burner to 
ground.
NOTE: “Earth” ground is not required.
Transformer: Add current ratings of module, gas 
control, vent damper and any other components of the 
control system to determine transformer size 
requirements.
Table 4. Specific Ignition Timings.
a
 Ignition Activation Period is the time that the hot surface igniter remains powered after the gas valve opens.
b 
Purge Timing specified in seconds.
Model
Ignition 
Type Draft Type
No. of 
Ignition 
Trials
Igniter/S
ensor 
Type
Automati
c Restart 
Time
Ignition 
Activatio
n Period
a
Prepurg
e 
Timing
b
Postpurg
e Timing
b
S9360A Intermittent 
Pilot - Spark
Induced Infinite Combined 1 hour N/A 30 0
S9360A Intermittent 
Pilot - Spark
Atmospheri
c
Infinite Combined 1 hour N/A 2.75 0