4. CROSS-DUCT EXCEL
The unit maximum power consumption and cable lengths are as follows:
Unit Type Maximum Power Maximum cable length (m) Maximum cable length (m)
consumption with 1.5mm
2
conductors with 2.5mm
2
conductors
(W) (12ohms/km) (7.6ohms/km)
Cross-Duct
(Transmitter + 13 340 540
Receiver)
Notes:
1. The control room supply voltage is assumed to be +24V.
2. All connections along the cable are sound and have zero resistance.
4.3.4 Unpacking
Carefully unpack the equipment, observing any instructions that may be printed on or contained
within the packaging.
Check the contents for damage and against the packing note for deficiencies. In the event of
damage or loss in transit, notify the carrier and Zellweger Analytics Limited or your local agent
immediately. The gas detector consists of the following items:
1 x Mounting Plate, 1 x Mounting Cell 2 x Mounting Straps Nuts, Bolts & Washers
1 x Isolation Kit
1 x Transmitter 1 x Receiver