MAN0530 Issue 10 - 11/09 Searchline Excel
2104M0506
5. PROBLEM SOLVING
Fault/Problem Causes Remedies
Diagnostics Receiver misaligned 1)Re-aligntheReceiver,rstusingthe
report telescope and then using the Interrogator.
Neg Gas 2) Re-zero the unit.
Reading
Contamination of windows 1) Check the Transmitter and Receiver
windows for build up of contamination.
Clean windows if required.
See Chapter 5.
2) Re-zero the unit.
Negative drift of unit’s zero Re-zero the unit.
position
Diagnostics
Receiver misaligned 1)Re-aligntheReceiver,rstusingthe
report telescope and then using the Interrogator.
Baseline Drift 2) Re-zero the unit.
Contamination of windows 1) Check the Transmitter and Receiver
windows for build up of contamination.
Clean windows if required.
2) Re-zero the unit.
Drift of unit’s baseline Re-zero the unit
Diagnostics Unit has been operated 1)WhenExcertiedequipmentis
report at a temperature outside operatedoutsideitscertiedrange,its
Bad itsspecied andcertiedrange typeapprovalcerticationisinvalidated
Temperature along with its warranty.
Such equipment should be removed from
service in potentially explosive
atmospheres.
2) Investigate the cause of the excessive
temperature excursion and take steps to
preventrecurrence.(e.g.tsunshadeor
heat-shield, or relocate detector, etc.)
Diagnostics Incorrect supply voltage 1)Checkthatthe+24Vsupplyvoltageis
report reaching unit reaching the unit
Supply Fault  (itshouldbebetween+18Vand+32V).
2) Identify the cause of incorrect supply
voltage reaching the unit and rectify.
Diagnostics Fault on the unit's digital If this fault is displayed when the unit is
report PCB interrogated, it cannot be remedied
DSP Fault intheeld.
Diagnostics A fault has been detected in If this fault is displayed when the unit is
report the NV-RAM interrogated, it cannot be remedied
NV-RAM Fault intheeld.
Diagnostics The time and date record 1) Re-enter the time and date using the
report being stored by the Real Interrogator.
RTC Fault Time Clock (RTC) has been 2) Cycle the power applied to the unit.
lost 3) Verify that the time and date record was
maintained after cycling the power.
Diagnostics Voltage reference fault If this fault is displayed when the unit is
report detected interrogated, it cannot be remedied in the
Volt Ref Fault eld.

Other manuals for Honeywell Searchline Excel

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell Searchline Excel and is the answer not in the manual?

Honeywell Searchline Excel Specifications

General IconGeneral
BrandHoneywell
ModelSearchline Excel
CategoryOther
LanguageEnglish

Related product manuals