MAN0530 Issue 10 - 11/09 Searchline Excel
2104M0506
• viewthesystemtype
• setthesystempathlength
• performasystemselftest
• checksystemalignment
• initialisethesystemandmakeitlive
Note: The 4-20 output is inhibited during this procedure. See the earlier description.
System Type
The initial display after Install is chosen is in the following format:
System Type
tttttttt
where: tttttttt System type. The system type displayed is one of the following:
Display Text System Type
Short Range 40m range system
Medium Range 120m range system
Long Range 200m range system
Duct Mount 0.5 - 5m range system
Note: It is not possible to change the system type. This is set during calibration and conguration
of the unit at the factory.
Path Length
The following message is displayed:
Path Length
nnnn
where: nnnn The path length in metres.
The following ranges of path length can be entered for the system types:
System Type Minimum Range (m) Maximum Range (m) Step Size (m)
Short Range 5 40 1
Medium Range 20 120 1
Long Range 120 200 1
Duct Mount 0.5 5 0.1
>
>
APPENDIX A - HANDHELD INTERROGATOR