Revision 4  Foundation Fieldbus RMA803 Remote Indicator User's Guide  Page 113 
Table 36: Setting the Simulation Jumper 
To  Set the Jumper to: 
Disable the SIMULATE parameter. 
(Set Remote Indicator for normal 
operation.)  
“OFF” position on the Transducer board. 
 
Enable the SIMULATE parameter. 
(For testing or debugging purposes.) 
 “ON” position on the Transducer board. 
 
 
Enabling simulation mode  
The SIMULATE parameter is enabled by setting the hardware simulation jumper to the “ON” 
position. 
Simulation mode truth table 
Table 37 shows the states of the simulation jumper and SIMULATE parameter shows how to 
activate the simulation mode. 
 
Table 37: Simulation Mode Truth Table 
When the Simulation 
Jumper 
(HW_SIMULATE_JUMPE
R_STATE) on Transducer 
board is set to: 
 and the SIMULATE Enable_Disable is set to: 
(Disabled)  (Active) 
 “OFF” Position  Simulation Disabled  Simulation Disabled 
“ON” Position  Simulation Disabled  Simulation Active