Page 18  Foundation Fieldbus RMA803 Remote Indicator User's Guide  Revision 4 
The Advanced Display Menus 
The Advanced Display menus are organized into three levels, as shown by Table 7. There is a 
<Return> menu item at each level that allows the user to return to the previous level. 
Table 7: Advanced Display Main Menu Structure 
Level 1  Level 2  Level 3 
<Exit> 
n/a  n/a 
Diagnostics 
Critical 
Non-Critical 
For details go to the Diagnostics Menu table. 
Display Setup 
LCD Contrast 
Common Setup 
Screen 1 
Screen 2 
… 
Screen 8 
For details go to the Display Setup Menu table. 
 
Note that the Advanced Display supports the 
configuration of up to 8 different screens. 
Note that only LCD Contrast, Rotation time, and 
Rotation Enable are editable parameters. Rest all are 
read only. 
Information 
Display 
Elec Module 
Model 
Options 
For details go to the Information Menu table. 
Table 8: Diagnostics Menu 
 
All Diagnostics menu items are Read Only. 
<Return>  Return to the Level 1 menu 
Critical 
<Return> 
Active Diags  # # 
Shows the number of Critical Diagnostics that 
are currently active. 
Elec. Module 
OK 
FAULT 
FAULT: There is a problem with the 
Electronics Fieldbus Communication Module. 
Non-
Critical 
<Return> 
Active Diags  # # 
Shows the number of Non-Critical Diagnostics 
that are currently active. 
Supply Voltage 
OK 
LOW 
HIGH 
OK: Supply voltage is within the specification 
limit 
LOW: Supply voltage is below the low 
specification limit 
HIGH: Supply voltage is above the high 
specification limit. 
Elec Module Temp 
OK 
OVER TEMP 
OVERTEMP:  Electronics temperature is 
greater than 85 Deg C