Revision 4 Foundation Fieldbus RMA803 Remote Indicator User's Guide Page 51
Parameters List
Table 18: LCD Transducer block parameters
Parameter Description
ST_REV
The revision level of the static data associated with the function
block.
TAG_DESC
The user description of the application of the block.
STRATEGY
Used to identify grouping of blocks.
ALERT_KEY The identification number of the plant unit.
MODE
The actual, target, permitted, and normal modes of the block.
BLOCK_ERR
This parameter reflects the error status associated with the
hardware or software components associated with a block. It is a
bit string, so that multiple errors may be shown.
UPDATE_EVT
This alert is generated by any change to the static data.
BLOCK_ALM
The BLOCK_ALM is used for all configuration, hardware, and
connection failure or system problems in the block. The cause of
the alert is entered in the subcode field. The first alert to become
active sets the Active status in the Status attribute. As soon as
the Unreported status is cleared by the alert reporting task,
another block alert may be reported without clearing the Active
status, if the subcode has changed.
DISP_SEQ_TIME
Periodic rotation time of the display screens in seconds. Range
3-30 sec.
LANGUAGE
Language selection for the Display. Supported Languages:
English, French, German, Spanish, Russian, Italian, Turkish,
Chinese, and Japanese.
DISPLAY_TYPE
Type of Display Connected. Possible Values: No Display
Connected, Advanced Display.
LCD_CONTRAST
Contrast of the LCD screen can be controlled by this parameter.
Its range is 1-9.
DISP_FW_VER Version Number of Display Firmware.
BLOCK_TYPE Block type selection for screen process value. The
BLOCK_TYPE is present in all the eight screens:
BLOCK_TYPE_1, BLOCK_TYPE_2, BLOCK_TYPE_3,
BLOCK_TYPE_4, BLOCK_TYPE_5, BLOCK_TYPE_6,
BLOCK_TYPE_7 and BLOCK_TYPE_8
PARAM_INDEX Parameter selection for screen process value. Parameters need
to be chosen based on Block type. The PARAM_INDEX is
present in all the eight screens: PARAM_INDEX_1,
PARAM_INDEX_2, PARAM_INDEX_3, PARAM_INDEX_4,
PARAM_INDEX_5, PARAM_INDEX_6, PARAM_INDEX_7 and
PARAM_INDEX_8.