Revision 4  Foundation Fieldbus RMA803 Remote Indicator User's Guide  Page 61 
Parameter  Description 
TRK_VAL   The value (after scaling from TRK_SCALE to OUT_SCALE) 
APPLIED to OUT in LO mode.  
FF_VAL   The feedforward control input value and status.  
FF_SCALE   The high and low scale values, engineering units code, and number 
of digits to the right of the decimal point associated with the 
feedforward value (FF_VAL).  
FF_GAIN   The feedforward gain value. FF_VAL is multiplied by FF_GAIN 
before it is added to the calculated control output.  
UPDATE_EVT   This alert is generated by any changes to the static data.  
BLOCK_ALM   The block alarm is used for all configuration, hardware, connection 
failure, or system problems in the block. The cause of the alert is 
entered in the subcode field. The first alert to become active sets the 
active status in the status parameter. As soon as the Unreported 
status is cleared by the alert reporting task and other block alert may 
be reported without clearing the Active status, if the subcode has 
changed.  
ALARM_SUM   The summary alarm is used for all process alarms in the block. The 
cause of the alert is entered in the subcode field. The first alert to 
become active sets the Active status in the Status parameter. As 
soon as the Unreported status is cleared by the alert reporting task, 
another block alert may be reported without clearing the Active 
status, if the subcode has changed.  
ACK_OPTION   Used to set auto acknowledgment of alarms.  
ALARM_HYS   The amount the alarm value must return to within the alarm limit 
before the associated active alarm condition clears.  
HI_HI_PRI   The priority of the HI HI Alarm.  
HI_HI-LIM   The setting for the alarm limit used to detect the HI HI alarm 
condition.  
HI_PRI   The priority of the HI alarm.  
HI_LIM   The setting for the alarm limit used to detect the HI alarm condition.  
LO_PRI   The priority of the LO alarm.  
LO_LIM   The setting for the alarm limit used to detect the LO alarm condition.  
LO_LO_PRI   The priority of the LO LO alarm.  
LO_LO_LIM   The setting for the alarm limit used to detect the LO LO alarm 
condition.  
DV_HI_PRI   The priority of the deviation high alarm.  
DV_HI_LIM   The setting for the alarm limit used to detect the deviation high alarm 
condition.  
DV_LO_PRI   The priority of the deviation low alarm.  
DV_LO_LIM   The setting for the alarm limit use to detect the deviation low alarm 
condition.