Page 76 Foundation Fieldbus RMA803 Remote Indicator User's Guide Revision 4
Parameter Description
RESET_IN Resets the totalizers
STOTAL Indicates the snapshot of OUT just before a reset
RTOTAL Indicates the totalization of “Bad” or “Bad” and “Uncertain” inputs,
according to INTEG_OPTIONS.
SRTOTAL The snapshot of RTOTAL just before a reset
SSP The snapshot of TOTAL_SP.
INTEG_TYPE Defines the type of counting (up or down) and the type of resetting
(demand or periodic)
INTEG_OPTIONS A bit string to configure the type of input (rate or accumulative) used in
each input, the flow direction to be considered in the totalization, the
status to be considered in TOTAL and if the totalization residue must
be used in the next batch (only when INTEG_TYPE=UP_AUTO or
DN_AUTO).
CLOCK_PER Establishes the period for periodic reset, in hours.
PRE_TRIP Adjusts the amount of mass, volume or energy that should set
OUT_PTRIP when the integration reaches (TOTAL_SP-PRE_TRIP)
when counting up of PRE_TRIP when counting down.
N_RESET Counts the number of resets. It cannot be written or reset.
PCT_INC Indicates the percentage of inputs with Good status compared to the
ones with Bad or Uncertain and Bad status.
GOOD_LIMIT Sets the limit for PCT_INC. Below this limit OUT receives the status
Good
UNCERTAIN_LIMIT Sets the limit for PCT_INC. Below this limit OUT receives the status
Uncertain
OP_CMD_INT Operator command RESET Resets the totalizer
OUTAGE_LIMIT The maximum tolerated duration for power failure
RESET_CONFIRM Momentary discrete value with can be written by a host to enable
further resets, if the option “Confirm reset” in INTEG_OPTIONS is
chosen.
UPDATE_EVT This alert is generated by any changes to the static data.
BLOCK_ALM Used for all configuration, hardware, connection failure, or system
problems in the block. The cause of the alert is entered in the subcode
field. The first alert to become active sets the active status in the
status parameter. As soon as the unreported status is cleared by the
alert reporting task other block alerts may be reported without clearing
the Active status, if the subcode has changed.
LICENSE_STATUS
_IT
License status of the function block.