SV9510/SV9520 SMARTVALVE™ SYSTEM CONTROLS
69-2014 10
LP, at the tank. Also shut off gas supply before 
disconnecting manometer and replacing plug. Repeat 
Gas Leak Test at plug with main burner operating.
NOTE: Check the inlet pressure before adjusting the 
pressure regulator.
1. Check the full rate manifold pressure listed on the 
appliance nameplate. Ignition system control full 
rate outlet pressure should match this rating.
2. With main burner operating, check the ignition 
system control flow rate using the meter clocking 
method or check pressure using a manometer 
connected to the outlet pressure tap on the ignition 
system control. See Fig. 4.
3. If necessary, adjust the pressure regulator to match 
the appliance rating. See Tables 7 and 8 for factory-
set nominal outlet pressure and adjustment range.
a. Remove the pressure regulator adjustment cap 
screw.
b. Using a screwdriver, turn the inner adjustment 
screw clockwise  to increase or 
counterclockwise     to decrease the gas 
pressure to the burner.
c. Always replace the cap screw and tighten firmly 
to prevent gas leakage.
4. If the desired outlet pressure or flow rate cannot be 
achieved by adjusting the ignition system control, 
check the ignition system control inlet pressure 
using a manometer at the ignition system control 
inlet pressure tap. If the inlet pressure is in the 
nominal range (see Tables 8A and 8B), replace the 
ignition system control. Otherwise, take the 
necessary steps to provide proper gas pressure to 
the control.
NOTE: If the burner firing rate is above the capacity (at 1 
in. wc pressure drop) of the control (see Table 3 
for capacities), it may not be possible to deliver 
the desired outlet pressure. This is an application 
issue, not a control failure. Take whatever steps 
are required to correct the situation.
5. STEP-OPENING PRESSURE REGULATORS 
ONLY. Carefully check the burner lightoff at step 
pressure. Make sure the burner lights smoothly and 
without flashback to the orifice. Make sure all ports 
remain lit. Cycle the burner several times, allowing 
at least 60 seconds between cycles for the 
regulator to resume the step function. Repeat after 
allowing the burner to cool. Readjust the full rate 
outlet pressure, if necessary, to improve lightoff 
characteristics.
Table 7. Pressure Regulator Specification Pressures (in. wc).
Table 8. Pressure Regulator Specification Pressures (kPa).
MAINTENANCE
WARNING
Fire or Explosion Hazard.
Can cause severe injury, death or property 
damage.
Do not attempt to take the control apart or clean it. 
Improper cleaning or reassembly can cause gas 
leakage.
Regular preventive maintenance is important in 
applications such as in the commercial cooking and 
agricultural and industrial industries that place a heavy 
load on system controls because:
• In many such applications, particularly commercial 
cooking, the equipment operates 100,000 to 200,000 
cycles per year. Such heavy cycling can wear out the 
gas control in one to two years.
• Exposure to water, dirt, chemicals and heat can 
damage the gas control and shut down the control 
system.
The maintenance program should include regular 
checkout of the control as outlined in the Startup and 
Checkout section, and the control system as described in 
the appliance manufacturer literature.
Maintenance frequency must be determined individually 
for each application. Some considerations are:
• Cycling frequency. Appliances that may cycle 200,000 
times annually should be checked monthly.
• Intermittent use. Appliances that are used seasonally 
should be checked before shutdown and again before 
the next use.
• Consequence of unexpected shutdown. Where the 
cost of an unexpected shutdown would be high, the 
system should be checked more often.
• Dusty, wet, or corrosive environment. Since these 
environments can cause the gas control to deteriorate 
more rapidly, the system should be checked more often.
The system should be replaced if:
• It does not perform properly on checkout or 
troubleshooting.
• The gas control is likely to have operated for more than 
200,000 cycles.
• The control is wet or looks as if it has been wet.
Model Type
Type of 
Gas
Nominal Inlet 
Pressure Range
Factory Set Nominal Outlet 
Pressure Setting Range
Step Full Rate Step Full Rate
Standard, Slow NAT 5.0-7.0 — 3.5 — 3.0-5.0
LP 12.0-14.0 — 10.0 — 8.0-12.0
Model Type
Type of 
Gas
Nominal Inlet 
Pressure Range
Factory Set Nominal Outlet 
Pressure Setting Range
Step Full Rate Step Full Rate
Standard, Slow NAT 1.2-1.7 — 0.9 — 0.7-1.2
LP 2.9-3.9 — 2.5 — 2.0-3.0