Revision 2.0 FOUNDATION Fieldbus ST 700 Pressure Transmitter User's Guide Page 109
Parameter Initial Value Valid Range Corrective Action
BYPASS 0 1:OFF, 2:ON Initial value is a configuration error.
Set value in valid range.
SHED_OPT 0 1-8 see Shed
Options in the FF
specs.)
Initial value is a configuration error.
Set value in valid range.
HI_HI_LIM
HI_LIM
+INF
+INF
PV_SCALE, +INF Values must be set in rank order. For
example, LO_LIM > LO_LO_LIM but <
HI_LIM etc.
LO_LIM
LO_LO_LIM
-INF
-INF
PV_SCALE, -INF Values must be set in rank order.
OUT_HI_LIM
OUT_LO_LIM
100
0
OUT_SCALE
+/- 10%
Verify that OUT_HI_LIM > OUT_LO_LIM.
SP_HI_LIM
SP_LO_LIM
100
0
PV_SCALE
+/- 10%
Verify that SP_HI_LIM > SP_LO_LIM.