Revision 2.0 FOUNDATION Fieldbus ST 700 Pressure Transmitter User's Guide Page 65
Parameters List
Table 15: Input Selector block parameters
Parameter Description
ST_REV The revision level of the static data associated with the function block.
The revision value increments each time a static parameter value in the
block is changed.
TAG_DESC The user description of the application of the block.
STRATEGY Used to identify grouping of blocks. This data is not checked or processed
by the block.
ALERT_KEY The identification number of the plant unit. This information may be used
in the host for sorting alarms, etc.
MODE_BLK The Actual, Target, Permitted, and Normal modes of the block.
Target: The mode to “go to”
Actual: The mode the “block is currently in”
Permitted: Allowed modes that target may take on
Normal: Most common mode for target
BLOCK_ERR This parameter reflects the error status associated with the hardware or
software components associated with a block. It is a bit string, so that
multiple errors may be shown.
OUT The block output value and status.
OUT_RANGE High and low scale values, engineering units code, and number of digits
to the right of the decimal point associated with OUT
GRANT_DENY Options for controlling access of host computers and local control panels
to operating, tuning, and alarm parameters of the block. Not used by
device.
STATUS_OPTI
ONS
It helps to select options for status handling and processing. The
supported status option for the integrator block is: “Use Uncertain as
Good”, “Uncertain if MAN mode.”
IN_1 The block input value and status.
IN_2 The block input value and status.
IN_3 The block input value and status.
IN_4 The block input value and status.
DISABLE_1 Parameter to switch off the input from being used. 0 - On, 1 - Off
DISABLE_2 Parameter to switch off the input from being used. 0 - On, 1 - Off
DISABLE_3 Parameter to switch off the input from being used. 0 - On, 1 - Off
DISABLE_4 Parameter to switch off the input from being used. 0 - On, 1 - Off
SELECT_TYPE Determines the selector action: First Good, Minimum, Maximum, Middle,
and Average.