Page 66 FOUNDATION Fieldbus ST 700 Pressure Transmitter User's Guide Revision 2.0
Parameter Description
MIN_GOOD The minimum number of inputs which are “Good” is less than the value of
MIN_GOOD then set the OUT status to “Bad”.
SELECTED The integer indicating the selected input number.
OP_SELECT An operator settable parameter to force a given input to be used.
UPDATE_EVT This alert is generated by any change to the static data.
BLOCK_ALM The block alarm is used for all configuration, hardware, connection failure,
or system problems in the block. The cause of the alert is entered in the
subcode field. The first alert to become active sets the Active status in the
Status parameter. As soon as the Unreported status is cleared by the
alert reporting task, another block alert may be reported without clearing
the Active status, if the subcode has changed.