Page 108 FOUNDATION Fieldbus ST 700 Pressure Transmitter User's Guide Revision 2.0
Resolving the block configuration errors
Table 30 lists the parameters of all the blocks that can cause the status bit of Block
Configuration Error to be set in their respective BLOCK_ERR parameters. The following
table provides the initial values and the valid range for the parameters.
ATTENTION
Block configuration errors can only be cleared if the function block is being
executed (running). One way of determining block execution is by doing a
series of two or three reads of the BLOCK_TEST parameter and confirming
that the first byte of the parameter is incrementing. This works, if the execute
rate is fast relative to the speed of reading BLOCK_TEST. A very slowly
executing block may not appear to execute as the parameters are updated
only when the block executes.
Table 30: Resolving block configuration errors
Parameter Initial Value Valid Range Corrective Action
ALERT_KEY 0 non-zero Initial Value is a configuration error.
Set value to non-zero number.
SIMULATE 1 (disabled) 1-2 (disabled -
enabled)
Set value in valid range.
XD_SCALE 0 to 100 inches
of water
EU_100 > EU_0,
UNITS_INDEX
matches output of
transducer block
Set values to valid range(s).
OUT_SCALE 0 to 100 inches
of water
EU_100 > EU_0 Set values to valid range.
CHANNEL 0 1-2 Initial Value is a configuration error.
Set value to valid range.
L_TYPE 0 (Uninitialize) 1,2,3 (direct, indirect,
sq. root)
Initial Value is a configuration error.
Set value to valid range.
PV_FTIME 0 0-200 Set value to valid range.
ALARM_HYS 0.5 (%) 0-50 (%) Set value to valid range.
HI_HI_PRI,
HI_PRI,
LO_LO_PRI,
LO_PRI
0 0-15 Set value to valid range.
HI_HI_LIM,
HI_LIM
+INF +INF or within
OUT_SCALE range
Set value to valid range.
LO_LIM,
LO_LO_LIM
-INF -INF or within
OUT_SCALE range
Set value to valid range.