EasyManua.ls Logo

Honeywell ST700 - 3.11 Integrator block

Honeywell ST700
134 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Revision 2.0 FOUNDATION Fieldbus ST 700 Pressure Transmitter User's Guide Page 69
The usage is as follows:
Rate
It is used when the variable connected to the input is a rate, that is Kg/s, w, Gal/hour, and
so on. This input can come from the rate output OUT of an Analog Input block.
Accum
It is used when the input comes from the OUT_ACCUM output of a Pulse Input block,
which represents a continuous accumulation of pulse counts from a transducer, or from the
output of another Integrator block. The bits corresponding to IN_1 and IN_2 can be set to
False for Rate, or can be set to True for Accum.
If the input option is Rate
Each input needs a parameter to define the rate time unit: IN_1, IN_2. The time unit can be
selected in seconds/minutes/hours/days. The second analog input must be converted into
the same unit as that of the first input. IN_2 must be converted into the same units of IN_1.
This can be done by using the parameter UNIT_CONV. For example, if IN_1 is in seconds
and if IN_2 is in minutes, IN_2 must be converted to seconds before starting the
integration. In this case, the value of UNIT_CONV is .0166 (1/60).
To find the mass, volume, or energy increment per block execution, each rate must be
multiplied by the block execution time. This increment must be added or subtracted in a
register.
The following diagram is an example of the use of two Rate inputs:
Figure 13: Two Rate Inputs

Table of Contents

Related product manuals