EasyManua.ls Logo

Honeywell ST700 - Page 65

Honeywell ST700
134 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Revision 2.0 FOUNDATION Fieldbus ST 700 Pressure Transmitter User's Guide Page 51
Parameter Description
ALARM_HYS The amount the alarm value must return within the alarm limit before the
associated active alarm condition clears.
HI_HI_PRI The priority of the HI HI alarm.
HI_HI_LIM The setting for the alarm limit used to detect the HI HI alarm condition.
HI_PRI The priority of the HI alarm.
HI_LIM The setting for the alarm limit used to detect the HI alarm condition.
LO_PRI The priority of the LO alarm.
LO_LIM The setting for the alarm limit used to detect the LO alarm condition.
LO_LO_PRI The priority of the LO LO alarm.
LO_LO_LIM The setting for the alarm limit used to detect the LO LO alarm condition.
HI_HI_ALM The HI HI alarm data, which includes a value of the alarm, a timestamp of
occurrence and the state of the alarm.
HI_ALM The HI alarm data, which includes a value of the alarm, a timestamp of
occurrence and the state of the alarm.
LO_ALM The LO alarm data, which includes a value of the alarm, a timestamp of
occurrence and the state of the alarm.
LO_LO_ALM The LO LO alarm data, which includes a value of the alarm, a timestamp
of occurrence and the state of the alarm.

Table of Contents