TB3 SERIES COMMUNICATING THERMOSTATS INSTALLATION INSTRUCTIONS
21 31-00576-01
Binary Inputs
23
Analog
Value #23
0 to 3 Alarm
This parameter
indicates the alarm
state.
0 = No alarm
1 = Onboard Sensor
Alarm
2 = External Sensor
Alarm
3 = Changeover Sensor
Alarm
0 R COV
24
Analog
Value #24
2017 …2099 Current Year
This parameter adjusts
the current year.
2022 R/W -
25
Analog
Value #25
1 to 12
Current
Month
This parameter adjusts
the current month.
- R/W -
26
Analog
Value #26
1 to 31 Current Day
This parameter adjusts
the current day.
- R/W -
27
Analog
Value #27
00 to 23
Current
Hour
This parameter adjusts
the current hour.
- R/W -
28
Analog
Value #28
00 to 59
Current
Minute
This parameter adjusts
the current minute.
- R/W -
29
Analog
Value #29
1 to 4 Baudrate
1 = 9600bps
2 = 19200bps
3 = 38400bps
4 = 76800bps
4 R/W -
30
Analog
Value #30
1 to 9998
Parameter
Menu
Password.
This parameter adjusts
the password.
0 R/W -
31
Analog
Value #31
0 to 2
File Transfer
Process
Information.
0 = Firmware Confirmed
1 = Upload in Progress
2 = Upload Failed
0 R -
NO OBJECT VALUE
OBJECT
NAME
FUNCTION DEFAULT
READ (R)/
WRITE (W)
COV
PROPERTY
NO OBJECT VALUE
OBJECT
NAME
FUNCTION DEFAULT
READ (R)/
WRITE (W)
COV
PROPERTY
1
Binary
Input #1
0 to 1
Universal
Input Digital
Input Value
0 = Off
1 = On
- R COV