TB3 SERIES COMMUNICATING THERMOSTATS INSTALLATION INSTRUCTIONS
31-00576-01 22
Binary Values for TB3140x
Binary Values for TB3240x
NO OBJECT VALUE OBJECT NAME FUNCTION DEFAULT
READ (R)/
WRITE (W)
COV
PROPERTY
1
Binary
Value #1
0 to 1 Start/Stop
0 = Stop
1 = Start
1 R/W COV
2
Binary
Value #2
0 to 1
Celsius or
Fahrenheit
0 = Celsius
1 = Fahrenheit
0 R/W -
3
Binary
Value #3
0 to 1
Auto Mode
Enable
0 = Disable
1 = Enable
1 R/W COV
4
Binary
Value #4
0 to 1
Fan/Valve
Control
Selection
0 = Valve Independent
1 = Valve Dependent
1 R/W -
5
Binary
Value #5
0 to 1 VA1 Status
0 = Valve Closed
1 = Valve Opened
- R COV
6
Binary
Value #6
0 to 1 VA2 Status
0 = Valve Closed
1 = Valve Opened
- R COV
7
Binary
Value #7
0 to 1
Restore
Factory Setting
0 = Factory Setting Disable
1 = Factory Setting Started
0 R/W -
8
Binary
Value #8
0 to 1
Time Schedule
Local/Remote
Selection
0 = Time Schedule Local
Selected
1 = Time Schedule Remote
Selected Parameter will be
returned to 0 after 30 minutes
for security.
0 R/W -
NO OBJECT VALUE
OBJECT
NAME
FUNCTION DEFAULT
READ (R)/
WRITE (W)
COV
PROPERTY
1
Binary
Value #1
0 to 1 Start/Stop
0 = Stop
1 = Start
1 R/W COV
2
Binary
Value #2
0 to 1
Celsius or
Fahrenheit
0 = Celsius
1 = Fahrenheit
0 R/W -
3
Binary
Value #3
0 to 1
Auto Mode
Enable
0 = Disable
1 = Enable
1 R/W COV
4
Binary
Value #4
0 to 1
Fan/Valve
Control
Selection
0 = Valve Independent
1 = Valve Dependent
1 R/W -
5
Binary
Value #5
0 to 1
Restore
Factory
Setting
0 = Factory Setting Disable
1 = Factory Setting Started
0 R/W -
6
Binary
Value #6
0 to 1
Time
Schedule
Local/Remote
Selection
0 = Time Schedule Local Selected
1 = Time Schedule Remote
Selected Parameter will be
returned to 0 after 30 minutes for
security.
0 R/W -