TB7220U COMMERCIALPRO™ PROGRAMMABLE THERMOSTAT
62-0221—05 6
Heat Pump System Wiring
Fig. 13. Typical hookup of single-stage heat pump
with no auxiliary heat (1H/1C).
Fig. 14. Typical hookup of multistage heat pump with
no auxiliary heat (2H/2C).
Fig. 15. Typical hookup of single-stage heat pump
with auxiliary heat (2H/1C).
Fig. 16. Typical hookup of multistage heat pump
with auxiliary heat (3H/2C).
COMPRESSOR CONTACTOR
M23018
CHANGEOVER VALVE
1
2
3
4
5
FAN RELAY
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
PROTECTION AS REQUIRED.
FACTORY INSTALLED JUMPER.
WHEN USING BATTERIES, THE 24V COMMON CONNECTION
IS OPTIONAL.
"O/B" TERMINAL SET TO CONTROL AS EITHER "O" OR "B"
IN THE INSTALLER SETUP.
OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR.
WIRES MUST HAVE A CABLE SEPARATE FROM THE
THERMOSTAT CABLE.
OUTDOOR/INDOOR
TEMPERATURE
SENSOR
3
L1
(HOT)
L2
1
24 VAC
5
ECONOMIZER
C
G
Y
O/B
RC
R
W1
Y2
A
S1
S2
4
2
COMPRESSOR 1
COMPRESSOR 2
M23019
CHANGEOVER VALVE
FAN RELAY
1
2
3
4
5
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
PROTECTION AS REQUIRED.
FACTORY INSTALLED JUMPER.
WHEN USING BATTERIES, THE 24V COMMON CONNECTION
IS OPTIONAL.
"O/B" TERMINAL SET TO CONTROL AS EITHER "O" OR "B"
IN THE INSTALLER SETUP.
OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR.
WIRES MUST HAVE A CABLE SEPARATE FROM THE
THERMOSTAT CABLE.
OUTDOOR/INDOOR
TEMPERATURE
SENSOR
3
L1
(HOT)
L2
1
24 VAC
5
ECONOMIZER
C
G
Y
O/B
RC
R
W1
Y2
A
S1
S2
4
2
COMPRESSOR CONTACTOR
ECONOMIZER
M23020
CHANGEOVER VALVE
1
2
3
4
5
FAN RELAY
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
PROTECTION AS REQUIRED.
FACTORY INSTALLED JUMPER.
WHEN USING BATTERIES, THE 24V COMMON CONNECTION
IS OPTIONAL.
"O/B" TERMINAL SET TO CONTROL AS EITHER "O" OR "B"
IN THE INSTALLER SETUP.
OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR.
WIRES MUST HAVE A CABLE SEPARATE FROM THE
THERMOSTAT CABLE.
OUTDOOR/INDOOR
TEMPERATURE
SENSOR
3
L1
(HOT)
L2
1
24 VAC
5
AUXILIARY HEAT RELAY
C
G
Y
O/B
RC
R
W1
Y2
A
S1
S2
4
2
COMPRESSOR 1
COMPRESSOR 2
M23021
CHANGEOVER VALVE
FAN RELAY
1
2
3
4
5
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
PROTECTION AS REQUIRED.
FACTORY INSTALLED JUMPER.
WHEN USING BATTERIES, THE 24V COMMON CONNECTION
IS OPTIONAL.
"O/B" TERMINAL SET TO CONTROL AS EITHER "O" OR "B"
IN THE INSTALLER SETUP.
OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR.
WIRES MUST HAVE A CABLE SEPARATE FROM THE
THERMOSTAT CABLE.
OUTDOOR/INDOOR
TEMPERATURE
SENSOR
3
L1
(HOT)
L2
1
24 VAC
5
ECONOMIZER
AUXILIARY HEAT RELAY
C
G
Y
O/B
RC
R
W1
Y2
A
S1
S2
4
2