UNIPOINT OPERATING MANUAL 2306M5001 MAN0638 ISSUE 7 01/2011
16
9 Conguration
From normal mode press the st buttons together to enter conguration mode. If no password has been set the display will go directly to the menu
selection. If a password has been set then the display will show ‘OOO’ and the 1st digit will ash. Press st to change the rst digit of the password.
Press 3 to move to the next digit. Repeat to set the 2nd and 3rd digits of the password. Press x at any time to exit and return to normal mode. Press
3 after setting the 3rd digit to conrm the password and enter the menu selection. If the password entered is incorrect the display will return to normal
mode. Use the table below to help navigate the menu and make conguration changes.

OK

OK

OK

OK

OK
RANGE AND
UNITS (FS)*
3
RANGE FLASHES. PRESS 
TO SELECT NEW RANGE
3
UNITS FLASH. PRESS  TO SELECT NEW UNITS.
3
NEW RANGE AND UNITS SETTINGS CONFIRMED.
RETURNS TO MAIN MENU
SET ZERO
(0)**
3
CURRENT ZERO GAS READING DISPLAYED.
APPLY ZERO GAS.
3
'---' DISPLAYED WHILE MEASURING THEN ZERO
READING DISPLAYED. IF ZERO FAILS 'FFF' IS
DISPLAYED. REMOVE GAS.
3
NEW ZERO SETTING CONFIRMED. RETURNS TO
MAIN MENU
SET SPAN
(S)**
3
50% OF RANGE FLASHES.
PRESS 
TO SET CAL GAS CONCENTRATION
3
APPLY CALIBRATION GAS. LIVE GAS READING
DISPLAYED. 'S-L' IF TOO LOW, 'S-H' IF TOO HIGH.
3
'---' DISPLAYED WHILE MEASURING THEN NEW
SPANNED READING. IF SPAN FAILS 'FFF' IS
DISPLAYED. REMOVE GAS
3
NEW SPAN SETTING CONFIRMED. RETURNS
TO MAIN MENU
SET ALARMS
(A1, A2, A3)
3
CURRENT ALARM 1 SET POINT FLASHES. PRESS
 TO CHANGE.
3
PRESS  TO SELECT ALARM ON DELAY
(0 to 900 secs)
3
PRESS  TO SELECT ALARM OFF DELAY (0 to
900 secs)
3
ALARM 1 RELAY CONFIGURATION DISPLAYED.
PRESS  TO SELECT 'F'=FALLING OR
'r'=RISING
3
PRESS  TO SELECT 'E'=ENERGIZED OR
'd'=DE-ENERGIZED.
3
PRESS  TO SELECT 'L'=LATCHING OR 'n'=NON-
LATCHING
3
NEW ALARM SETTINGS CONFIRMED. RETURNS TO
MAIN MENU. REPEAT FOR ALARM 2 & 3.
SET FAULT
RELAY (F)
3
FIRST FAULT RELAY SETIING FLASHES. PRESS
 TO SELECT 'E'=ENERGIZED OR 'd'=DE-
ENERGIZED.
3
PRESS  TO SELECT 'IF'=FAULT RELAY ACTION
ON INHIBIT OR 'In'=NO ACTION ON INHIBIT.
3
NEW FAULT RELAY SETTINGS CONFIRMED. RETURNS
TO MAIN MENU
SET PASS-
WORD (PAS)
3
FIRST DIGIT OF CURRENT PASSWORD FLASHES.
PRESS  TO CHANGE FIRST DIGIT.
3
SECOND DIGIT OF PASSWORD FLASHES. PRESS 
TO CHANGE SECOND DIGIT.
3
THIRD DIGIT OF PASSWORD FLASHES. PRESS 
TO CHANGE THIRD DIGIT.
3
NEW PASSWORD CONFIRMED. RETURNS TO
MAIN MENU
DISABLE (dIS)
3
DISPLAY SHOWS ‘dIS’
3
LOWER LINE OF DISPLAY SHOWS 'OFF'. PRESS X AND
3 SIMULTANEOUSLY FOR >1 SECOND TO TAKE UNIT
OUT OF INHIBIT.
FIELD INHIBIT
(FIh)***
3
PRESS  TO SELECT 'Inh'= DETECTOR IN-
HIBIT ON OR 'FAL' FOR DETECTOR INHIBIT OFF
3
DETECTOR INHIBIT SETTING CONFIRMED. RETURNS
TO MAIN MENU.
NOTES:
Detector inhibit signal range = 1.5mA to 2.5mA.
All steps in the respective menu option must be completed and 3 pressed for the changes to be saved. Pressing X before confirmation of
new settings returns to main menu with no changes to configuration.
*See section 9 for available ranges and units.
**If configuring the controller for use with an Oxygen detector, skip the ‘Set zero’ instructions and use 20.9% (background air oxygen level)
as the span calibration point.
***Only available on mA input version
DETECTOR
TYPE (IP)***
3
CURRENT DETECTOR INPUT TYPE FLASHES.
PRESS  TO SELECT '2L'= 2 WIRE mA OR
'3L'=3 WIRE mA
3
DETECTOR INPUT SETTING CONFIRMED. RETURNS TO
MAIN MENU.

OK

OK

OK

OK

OK