Specication
Use The Unipoint controller provides integrators with a exible and low cost solution to the many applications
requiring ammable, toxic or oxygen gas detection to be incorporated into their control systems. Unipoint
is designed to use industry standard DIN rail allowing it to be easily installed into many different types of
plastic or metal, indoor or outdoor, hazardous or non hazardous area enclosures. It is designed for use
with any mV ammable gas detector as well as any 2 or 3 wire 4-20mA gas detector (subject to overall
power requirements).
User interface
Operation Two pushbuttons for normal operation of resetting alarms and initiating self diagnostic test of system.
Four buttons for user programmable functions via intuitive menu
Backlit display Units of measure, digital gas reading and event code
Other indication Ultra-bright steady/ashing LEDs subject to condition; alarm (red), power (green), fault (amber). In-built
audible alarm 63dB at 0.3 meters.
Termination
Easily accessible plug in screw type terminals. Terminals accept maximum wire diameter 1.5mm
2
Environmental
IP Rating IP30 (Install in suitable enclosure)
Weight 225g (Controller only)
Operational
Temperature
Humidity
Pressure
-10
o
C to +55
o
C / 14
o
F to 131
o
F (Performance approval -10°C to +40°C / 14°F to 104°F)
10 to 90%RH (non condensing)
90-110kPa
Storage -25°C to +60°C / -13°F to +140°F, 20 to 80%RH (non condensing)
Inputs
Supply Nominal 24Vdc (18-32Vdc). Max power mV = 4.8W (including power to detector), mA= 3.0W (excluding
power to 3 wire detector).
Detector type 3 wire mV bridge
e.g. Sensepoint or
Signalpoint ammable
gas detectors
2 wire, 4-20mA, loop
powered e.g. Sensepoint
or Signalpoint toxic or
oxygen gas detectors
3 wire, 4-20mA, source output e.g. Sensepoint Plus
and Pro ammable, toxic and oxygen gas detectors
Detector supply 2.4-8.6V, 200mA
constant current.
Maximum loop
resistance: 28 Ohms
Input (18-32Vdc)-1.5Vdc,
30mA max.
Input (18-32Vdc)-1.5Vdc, 0.5A max.
Outputs
Relays Alarm 1 Alarm 2 Alarm 3 Fault
Rating SPCO / 3A,
240Vac/30Vdc
(non inductive load)
SPCO / 3A,
240Vac/30Vdc
(non inductive load)
SPCO / 3A,
240Vac/30Vdc
(non inductive load)
SPCO / 3A,
240Vac/30Vdc
(non inductive load)
Default setting Non Latching
Normally de-energized
Energize on alarm
Factory setting 10%FSD
Non Latching
Normally de-energized
Energize on alarm
Factory setting 25%FSD
Latching (mV)
Non Latching (mA)
Normally de-energized
Energize on alarm
Factory setting 50%FSD
Non Latching
Normally energized
De-energize on fault/
power loss
User congurable options Latching/non-latching
Energized/de-energized
Alarm trip point
Rising/falling
Alarm on / off delay (0 to
900 seconds)
Latching/non-latching
Energized/de-energized
Alarm trip point Ris-
ing/falling
Alarm on / off delay (0 to
900 seconds)
Latching/non-latching
Energized/de-energized
Alarm trip point
Rising/falling
Alarm on / off delay (0 to
900 seconds)
Latching/non-latching
Energized/de-energized
Approvals
EMC/RFI EN50270
Electrical safety EN61010
Performance ATEX measuring function EN60079-29-1
SIRA10ATEX8243X
Other CE, TUV.