VISTA-15P/20P/SIA Installation and Setup Guide
7
Mounting and Wiring the Control (Continued)
Set device addresses. Refer to the instructions included with the devices and set each
address according to the Table of Device Addresses.
See data fields *190-*196 in the Programming Guide for details on enabling keypad
addresses, assigning keypad partitions, and selecting keypad sounding options.
IMPORTANT: Each keypad must be assigned a unique, predefined address, from 16 to 23.
The first keypad is address 16 (default = partition 1, all sounds enabled).
TOUCH SCREEN KEYPAD (AUI) NOTES:
Use of AUI devices (e.g., 6280, Tuxedo) is independent from standard keypads and does
not affect the number of standard keypads the system can support.
AUI devices must be set for address 1, 2, 5**, or 6** depending on which unit is enabled in
field *189. ** VISTA-20P series
Communication Device
(Long Range Radio)
Connections
Connect the data in/data out terminals and voltage input terminals of the communication
device to the control's keypad connection points.
Set the device’s address to “03” following the instructions provided with the device.
Use a compatible AlarmNet communicator.
Wire Run Chart for Devices* Drawing Aux Power from the Control (12V+ & 12V–)
TOTAL CURRENT DRAWN BY ALL DEVICES CONNECTED TO A SINGLE WIRE RUN
* Includes Keypads, RF Receivers, Zone Expander/Relay Units, and Communication Device.
Maximum wire lengths for any device that is homerun to the control can also be determined from the Wiring Run Chart, based on the
current draw of that device alone.
The length of all wire runs for both partitions combined must not exceed 1500 feet (457m) when unshielded quad conductor cable is used
(750 feet if shielded cable is used). This restriction is due to the capacitive effect on the data lines when quad cable is used.
Table of Device Addresses
*56 zone programming: input device type entry
automatic if AUI enable field *189 enabled for AUI 1
automatic if AUI enable field *189 enabled for AUI 2
AUI 3 (touchscreen) (V20P)
automatic if AUI enable field *189 enabled for AUI 3
AUI 4 (touchscreen) (V20P)
automatic if AUI enable field *189 enabled for AUI 4
Communication Device (LRR)
automatic if communication device is enabled in field *29
Zone Expanders (4219/4229):
Module 1 (for zones 09 - 16)
Module 2 (for zones 17 - 24)
Module 3 (for zones 25 - 32)
Module 4 zones 33 - 40
Module 5 zones 41 - 48
*56 zone programming: input device type, entry 2, then:
automatic if zone no. 9-16 set as AW type or relay assigned
automatic if zone no. 17-24 set as AW type or relay assigned
automatic if zone no. 25-32 set as AW type or relay assigned
automatic if zone no. 33-40 set as AW type or relay assigned
automatic if zone no. 41-48 set as AW type or relay assigned
Relay Modules (4204):
Module 1
Module 2
Module 3
Module 4
*79 output device programming: device address prompt:
entered at device address prompt
entered at device address prompt
entered at device address prompt
entered at device address prompt
Keypads:
Keypad 1
Keypad 2
Keypad 3
Keypad 4
Keypad 5
Keypad 6
Keypad 7
Keypad 8
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
data field programming as listed below:
always enabled for partition 1, all sounds enabled.
data field *190
data field *191
data field *192
data field *193
data field *194
data field *195
data field *196
** address 07 not available if zone-doubling enabled
† 4219/4229 addresses 9-11 and 4204 addresses 14-15 apply to the VISTA-20P.
†† Addressable devices are identified by “1” plus the device address when reporting. Enter report code for zone 91 to enable addressable device
reporting (default = reports enabled). See field *199 for addressable device 3-digit/2-digit identification keypad display options.