VISTA-15P/20P/SIA Installation and Setup Guide
15
System Communication and Operation (Continued)
Ademco Contact ID
®
The Ademco Contact ID
®
Reporting Format comprises the following:
4-digit or 10-digit subscriber number (depending on format selected).
1-digit event qualifier (“new” or “restore”).
3-digit event code.
2-digit Partition No.
3-digit zone number, user number, or system status number (see below).
Ademco Contact ID
®
Reporting takes the following format: CCCC(CCCCCC) Q EEE GG ZZZ
where: CCCC(CCCCCC) =Customer (subscriber) ID
Q = Event qualifier, where: E = new event , and R = restore
EEE = Event code (3 hexadecimal digits)
Note: For a complete list of event codes, refer to the central office receiver
manual.
GG = Partition Number (system messages show “00”)
ZZZ = Zone/contact ID number reporting the alarm, or user number for open/close
reports. System status messages (AC Loss, Walk Test, etc.) contain zeroes in
the ZZZ location.
TABLE OF CONTACT ID EVENT CODES
(some event codes may not apply to certain control panels)
Code
Definition
110
Fire Alarm
121
Duress
122
Alarm, 24-hour Silent
123
Alarm, 24-hour Audible
131
Alarm, Perimeter
132
Alarm, Interior
134
Alarm, Entry/Exit
135
Alarm, Day/Night; Wireless Tamper
Alarm while Armed
143
Alarm, Expansion Module
145
ECP Module cover tamper
146
Silent Burglary
150
Alarm, 24-Hour Auxiliary/Monitor zone
162
Carbon Monoxide
301
AC Power
302
Low System Battery/Battery Test Fail
305
System Reset (Log only)
321
Bell/Siren Trouble
333
Trouble, Expansion Mod. Supervision
341
Trouble, ECP Cover Tamper
344
RF Receiver Jam
351
Telco Line Fault
353
Long Range Radio Trouble
354
Failure to Communicate
373
Fire Loop Trouble
374
Exit Error Alarm
380
Global Trouble, Trouble Day/Night
Code
Definition
381
RF Sensor Supervision
382
Supervision Auxiliary Wire Zone
383
RF Sensor Tamper
384
RF Sensor Low-battery
393
Clean Me
401
R401 Armed AWAY / MAXIMUM
E401 - Disarmed
403
Schedule Arm/Disarm AWAY
406
Cancel by User
407
Remote Arm/Disarm (Downloading)
408
Quick Arm AWAY
409
Keyswitch Arm/Disarm AWAY
441
R441 Armed STAY / INSTANT
E441 Disarmed
Quick Arm STAY / INSTANT
442
Keyswitch Arm/Disarm STAY
455
Scheduled Arm Fail
459
Recent Closing (SIA panels only)
570
Bypass
601
Manually Triggered Dialer Test
602
Periodic Test
606
Listen to Follow
607
Walk Test Entered/Exited
623
Event Log 80% Full
625
Real-Time Clock was Changed (log only)
627
Program Mode Entry (log only)
628
Program Mode Exit (log only)
642
Latch Key (log only)
750 -
789
Reserved for Configurable Zone Type