11
Section 1: General Description
• • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • •
SIA Installations
The VISTA-32BPT is not certified as SIA compliant, but can be programmed for False Alarm Reduction. To program for
False Alarm Reduction, follow the SIA Guidelines noted in the applicable programming fields.
About the VISTA-32FBPT
The VISTA-32FBPT is a 2-partition, UL Listed commercial fire and burglary control panels that include the features
described below.
Features
Hardwire and Optional Expansion Zones
• Provides 8 hardwire zones.
• Supports up to 16 2-wire smoke detectors each on zone 1 and zone 2 (32 total).
• Automatically resets 4-wire smoke detectors if the Aux Relay is programmed for smoke reset (3*61 = 2).
• Triggers the built-in sounders on other hardwired smoke detectors if one smoke detector annunciates an alarm.
This feature requires a System Sensor RRS-MOD.
• Supports up to 24 additional expansion zones using a built-in polling (V-Plex) loop.
• Supports up to 32 wireless zones fewer if using hardwire and/or polling loop zones.
U
LC
Wireless devices are not ULC Listed and cannot be used in ULC Installations.
Peripheral Devices
• Supports up to 31 addressable devices, (keypads, RF receivers, relay modules, etc.).
• Supervises devices (keypads, RF receivers, and relay modules) and individual relays (up to 32), as well as
system zones.
Keypads
• 6160CR2 keypads for Fire applications
• 6160 keypads for Burglary applications
(Alpha keypads provide three panic key functions: 1 + ∗ (A), ∗ + # (B), and 3 + # (C).)
• Up to six 6280 Graphic/Touch-Screen keypads for burglary applications.
• AlarmNet Total Connect (Remote Interactive Service) allows access from a wireless smart phone or web browser
via any Total Connect 2 compatible AlarmNet device.
U
L
Use of Remote Interactive Service (Total Connect) is not permitted in UL installations.
NOTE: If using Total Connect Remote Interactive Services, the virtual keypad must be assigned to a burglary
partition, and the GOTO feature (program field 2∗18) must be “0” (disabled) for partition 1 (the fire partition) so that
the Fire system cannot be accessed remotely. This is the system default setting.