Supplementary Power Supply for Additional Keypads
When the control’s auxiliary power load for all devices exceeds 1A, you can power additional keypads from a regulated
12VDC power supply. Use a UL Listed, battery-backed supply for UL installations. For fire applications, the power
supply must be UL1481 Listed.
Connect the additional keypads as shown in Figure 3-9, using the keypad wire colors shown. Be sure to observe the
current ratings for the power supply used.
U
L
For UL commercial fire and burglary installations, no more than one wire per terminal may be connected.
Use only 14-22AWG wire.
Make connections directly to the screw terminals as shown in Figure 3-9.
Be sure to connect the negative (–) terminal on the power supply unit to terminal 7 () on the control.
+
11 12 13 14
SUPPLEMENTARY
POWER SUPPLY
SUPPLEMENTARY
POWER SUPPLY
–
+
+
–
–
–
+
–
CONTROL TERMINAL STRIP
A
UX.
AUX. DATA
IN
DATA
OUT
IMPORTANT:
MAKE CONNECTIONS
DIRECTLY TO SCREW
TERMINALS AS SHOWN.
MAKE NO CONNECTION
TO THE KEYPAD BLUE
WIRE (IF PRESENT).
YEL
GRN
+
+
+
–
–
YEL
YEL
GRN
GRN
YEL
GRN
TO KEYPAD BLK WIRE
TO KEYPAD RED WIRE
TO KEYPAD GRN WIRE
TO KEYPAD YEL WIRE
pwr_sup_conn-010-V0
TO BURG DEVICES
TO FIRE DEVICES
TO BURG DEVICES
BURG DEVICES
FIRE DEVICES
TO FIRE DEVICES
ECP ISOLATOR
OUT IN
Figure 3-9. Using a Supplementary Power Supply
Installing External Sounders
The VISTA-32FBPT provides two Notification Appliance Circuits for operating fire and burglary alarm notification
appliances. Each circuit is rated as Special Application for Fire and 10VDC – 14VDC, 1.7A max. power-limited for
Burglary.
NOTE: The total alarm current drawn from Auxiliary Power 1, Auxiliary Power 2, polling loop, Bell 1, and Bell 2 cannot
exceed 2.3A (for Canada 1.95A) for battery-independent operation.
The outputs have the following options:
Selectable to activate by individual zone assignments
Selectable for confirmation of arming ding.
Selectable to chime when entry/exit or perimeter zones are faulted.
Selectable for no timeout or timeout of 2-30 minutes.
You may use a Commercial Fire Listed 24VDC Power Supply to convert one or both VISTA-32FBPT 12VDC,
1.7A style-Y supervised Special Application Notification Appliance Circuits to 24V, style-Y supervised, Special
Application Notification Appliance Circuits.