WEEKLY TESTING IS REQUIRED
TO ENSURE PROPER OPERATION
OF THIS SYSTEM.
POLE Door Strike/Mag Coil
DATA 1 (WHITE)
DATA 0 (GREEN)
NOTE 1: USE UL LISTED ENERGY CABLE FOR ALL CONNECTIONS.
NOTE 2: VISTAKEY TB3 TERMINAL 5 IS A GROUND AND MAY BE
USED INSTEAD OF TB3 TERMINAL 2. TB3 TERMINALS 2 AND 5 ARE
A COMMON GROUND.
NOTE 3: WHEN USING TRIGGER TO TURN ON AN LED OR BUZZER,
RETURN HIGH SIDE OF LED OR BUZZER TO TB3 TERMINAL 7.
TRIGGER RATING IS 15mA AT 12VDC.
+5V
GND
TRIGGER (SEE NOTE 3)
+12V (RED)
ZONE C (General)
ZONE A (DSM)
ZONE B (RTE)
POLLING LOOP -
14V MAX (12V @ 85-160mA Nominal)
POLLING LOOP +
GND
GND
GND
N/O DOOR STRIKE POWER
N/C MAG COIL POWER
2
3
4
5
6
7
8
11 122 3 4 5 6 7 8 9 101
RELAY CONTACT RATINGS:
3A @ 28VDC MAX. (RESISTIVE LOAD)
TB 1
TB 3
1
READER INTERFACE CABLE
GND (BLACK)
RDR LED (ORANGE)
TO ALARM SYSTEM
CONTROL PANEL
POLLING LOOP TERMINALS.
NO
CONNECTION
VISTAKEY
THIS DEVICE COMPLIES WITH PART 15 CLASS A
LIMITS OF FCC RULES. OPERATION IS SUBJECT
TO THE FOLLOWING TWO CONDITIONS:
(1) IT MAY NOT CAUSE HARMFUL INTERFERENCE.
(2) IT MUST ACCEPT ANY INTERFERENCE THAT
MAY CAUSE UNDESIRED OPERATION.
K1
DOOR
CONTROL
RELAY
FOR ADDITIONAL RATINGS AND
SPECIFICATIONS, REFER TO
INSTALLATION INSTRUCTION
FOR THE VISTAKEY-SK.
THIS EQUIPMENT SHOULD BE INSTALLED IN
ACCORDANCE WITH THE NATIONAL FIRE
PROTECTION ASSOCIATION'S STANDARDS 70 &
74 (NATIONAL FIRE PROTECTION ASSOC.,
BATTERYMARCH PARK, QUINCY, MA. 02269).
PRINTED INFORMATION DESCRIBING PROPER
MAINTENANCE, EVACUATION PLANNING AND
REPAIR SERVICE IS TO BE PROVIDED WITH
THIS EQUIPMENT.
TO TB1, 11 OR 12
+ 12 VDC TO ONLY
ONE OF THESE INPUTS.
(FROM TB1-1)
Figure 3-26: Wiring the VistaKey
Event Log Connections
This system has the ability to record up to 512 events of various categories in the Event Log (history log) of various
categories in the Event Log (history log). Each event is recorded with the time and date of its occurrence (if real-time
clock is set).
The categories are Alarm, Supervisory/Check, Bypass, Open/Close, System and Test conditions. The log may be viewed
on an alpha keypad, the GUI or printed on a serial printer.
NOTE: If you are using a serial printer, it must configured with 7 data bits, even parity, 1 stop bit, 9600 baud
Installing the 4286 VIP Module
The 4286 VIP Module is an add-on accessory that permits the user to access the security system (and relays) via a
TouchTone telephone. This may be done either from the premises or by calling the premises from a remote location.
Only one VIP Module can be used in a security system. This module must be enabled as Device Address 4 in the Device
Programming in #93 Menu Mode, and must be assigned to a partition.
U
L
The 4286 VIP Module is not permitted in UL installations.